Product overview and specifications – Dell Basic PDU User Manual
Page 2

2
Dell Basic Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Basic Rack PDU distributes power to the devices in the rack.
O
U T L E T S
— The Rack PDU has eight (8) C13 outlets.
P
O W E R
C O R D
— The Rack PDU has an IEC-320 C14 inlet and can be used with a detached power cord (not provided).
J541N
Electrical
Input connection
IEC-320 C14 inlet
Acceptable input voltage
100–240 VAC
±
10% (UL(C-UL))
200–240 VAC
±
10% (International)
Maximum input current (phase)
15 A (12 A UL(C-UL) derated)
10 A (International)
Input frequency
50/60 Hz
Output voltage
100–240 VAC
±
10% (UL(C-UL))
200–240 VAC
±
10% (International)
Output connections
(8) C13
Maximum output current (outlet)
C13; 12 A (UL(C-UL) derated)
C13; 10 A (International)
Maximum output current (phase)
12 A (UL(C-UL) derated)
10 A (International)
Physical
Dimensions
(H x W x D)
23.97 x 4.36 x 9.29 cm
(9.44 x 1.72 x 3.66 in)
Shipping dimensions
(H x W x D)
28.60 x 21.03 x 13.00 cm
(11.26 x 8.28 x 5.12 in)
Weight
0.90 kg (2.00 lb)
Shipping weight
1.37 kg (3.01 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing
Compliance
Safety approvals
UL(C-UL), VDE, IRAM, SABS, GOST-R,
SONCAP, KC, CE
ROHS
Dell 6T198
EU DIRECTIVE 2002/95/EC–latest revision