Product Overview and Specifications

The Dell Metered Rack PDU distributes power to the devices in the rack.

O

UTLETS—

The Rack PDU has (18) IEC 320-C13 and (12) IEC 320-C19 outlets.

P

OWER

CORD—

The Rack PDU attached power cord terminates with a 5-pin, 3

f, IEC60309 plug, 530P6S or 532P6S.

DELLM0002

Electrical

Input connection

NA: IEC60309-30 A plug; INTL: IEC60309-32 A plug

Acceptable input voltage

346–415 VAC

± 10%

Maximum input current (phase)

NA: 30 A (24 A UL(C-UL) derated); INTL: 32 A

Input power

22 kVA

Input frequency

50/60 Hz

Output voltage

200–240 VAC

± 10%

Output connections

(18) IEC 320-C13
(12) IEC 320-C19

Maximum output current (outlet)

C13: 10 A
C19: 16 A

Maximum output current (phase)

NA: 30 A (24 A UL(C-UL) derated); INTL: 32 A

Maximum output current (total all
output)

NA: 72 A (maximum); INTL: 96 A (maximum)

Maximum output current (breaker)

20 A

Physical

Dimensions
(H

W

D)

178.0

5.6

5.1 cm

(70.1

2.2

2.0 in)

Depth at breakers: 9.3 cm (3.7 in)

Shipping dimensions
(H

W

D)

200.0

20.0

17.0 cm

(78.7

7.9

6.7 in)

Weight

7.0 kg (15.4 lb)

Shipping weight

9.4 kg (20.7 lb)

Information in this document is subject to change without notice.
© 2010–2012 Dell Inc. All rights reserved.

Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden.

Trademarks used in this text:

Dell and the DELL logo are trademarks of Dell Inc.

Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in
trademarks and trade names other than its own.

Model DELLM0002

2/2012 • 164202130 Rev 2