To avoid injury and damage to persons and
devices, it is absolutely necessary these
instructions and Safety notes attached are
carefully read and observed prior to assembly
and commissioning.
Do not dismantle actuators with safety spring
function! Danger of injury and life in case of
improper handling!
Actuator is heavy. Handle with care to avoid
injury or product damage.
Wiring
Do not touch anything on the PCB! Do not
remove the service cover before the power
supply is fully switched off.
Max. allowed current output on terminals
4 and 5 is 4 A.
DIP switch setting
DIP1: FAST/SLOW – Speed selection ①
- FAST position; 3 (4) s/mm
- SLOW position; 6 s/mm
DIP2: DIR/INV – Direct or inverse acting
selector ②
- DIR position; the actuator is direct acting
- INV position; the actuator is inverse acting
Functions accessible from cover
RESET button ❼
(versions AMV 658/659)
Press the RESET button (press once) to enter
Stand-By mode. The actuator stops in current
position and stops responding to any control
signal. Red light is constantly lit. You can now
manually operate the actuator. This mode can
be very useful during the commissioning of
other equipment, or for service purposes.
To exit Stand-By mode press the RESET button
again.
Manual operation
Mechanical and electrical operation are
not allowed to be used at the same time!
Actuator AMV 655 can be manually positioned
any time and it remains in selected position
until it receives signal from the controller.
Actuators AMV 658 can be manually positioned
when in Stand-By mode or when there is no
power supply (mechanically).
Actuators AMV 659 can be manually positioned
only in Stand-By mode.
Actuator
type
Mechanical
operation
Electrical
operation
AMV 655
AMV 658
AMV 659
Mechanical manual operation A
Actuators AMV 655/658 have a manual
operation knob on the top of the housing which
enables hand positioning of the actuator.
Mechanical manual operation shall be
used only when no power supply.
Electrical manual operation B
Actuators AMV 658/659 have two buttons
on the top of the housing that are used for
electrical manual positioning (up or down)
when the actuator is in Stand-By mode. First
press the RESET button until the actuator goes
to Stand-By mode (red LED is lit). By pressing the
upper button
the stem will be extracted
and by pressing the lower button
the stem
will be retracted.
Installation Guide
AMV 655 / 658 SD / 658 SU / 659 SD
District Energy
VI.LE.L2.0C
DEN-SMT/SI
ENGLISH