beautypg.com

Figure-7 two actuators on the same damper shaft – Schneider Electric MS40-717X User Manual

Page 6

background image

6

© Copyright 2010 Schneider Electric All Rights Reserved.

F-26748-6

MS40-7173

Red

Black

24H (DC+)

24G (DC-)

24 Vac Transformer

or 22-30 Vdc

GRD

Green/Yellow

4 to 20 mA

Yellow/Black

Gray

AI

COM

+

-

500 Ohm

1

Position Feedback (-)

Signal 2 to 10 Vdc (+)

Blue

AO

Control

Signal

1 Unused conduit port must remain plugged with a water

tight pipe plug as shipped from factory to maintain
NEMA Type 4 or IP56 rating.

2 Color coding of wiring on older models (MX40-717x-0-

0-0) manufactured prior to December, 2007, differs
from current models. See Table 4 on page 14. Consult
label on product to confirm wiring codes.

3 Keep AI, COM and AO wiring less than 30 meters

length to meet CE requirements.

2

3

Figure-6 Typical MS40-7173 4 to 20 mA Wiring Diagram.

2 to 10 Vdc

Control

Signal

GRD

MS40-717X

Power

GRD

1

1

2

MS40-717X

1 Unused conduit port must remain plugged with a

water tight pipe plug as shipped from factory to
maintain NEMA Type 4 or IP56 rating.

2 See table for power wire designations.

3 Both actuators must be set to operate in the same

direction.

3

3

(+)

(-)

Yellow/Black

AI

Gray COM

Blue

AO

Yellow/Black

AI

Gray COM

Blue

AO

Position Feedback (-)

Signal 2 to 10 Vdc (+)

4 Color coding of wiring on older models (MX40-717x-0-

0-0) manufactured prior to December, 2007, differs
from current models. See Table 4 on page 14. Consult
label on product to confirm wiring codes.

5 Keep AI, COM and AO wiring less than 30 meters

length to meed CE requirements.

4

4

5

5

Green/Yellow

Green/Yellow

Power Wiring Identification.

Voltage

Designation

Wire Color

24 Vac or

22-30 Vdc

24H (DC+)

Red

24G (DC-)

Black

120 Vac

L1

Black

L2

White

240 Vac

L1

Brown

L2

Light Blue

Figure-7 Two Actuators on the Same Damper Shaft.