NOTE:Do not exceed minimum/maximum CFM limits shown under Air

Flow Data.

APPLICATION LIMITATIONS

These units must be installed in accordance with all national and
local safety codes.

Air flow must be within the minimum and maximum limits approved
for electric heat, evaporator coils and outdoor units.

COOLING CAPACITY - Coil Only

*

MODEL

RATED

CFM

ENTERING

AIR

°F

(Wet Bulb)

MBH @ Evaporator Temperature and Corresponding Pressure °F/ PSIG

35 / 61.5

40 / 68.5

45 / 76.0

50 / 84.0

HORIZONTAL DUCT TYPE

HD24S**H1

815

72

35.3

32.4

28.7

24.9

67

32.6

29.4

26.0

22.5

62

26.7

23.7

20.5

17.2

57

21.7

18.8

15.7

12.3

HD36S**H1

1192

72

57.9

52.7

47.1

41.5

67

46.4

41.1

35.9

30.4

62

36.2

30.4

26.5

24.7

57

31.1

28.7

26.5

24.7

HD48S**H1

1610

72

83.4

71.7

59.7

47.1

67

66.8

56.1

45.6

34.9

62

52.1

41.5

33.7

28.3

57

44.7

39.2

33.7

28.3

HD60S**H1

2100

72

133.0

112.4

90.9

69.2

67

106.5

87.9

69.4

50.0

62

83.0

65.0

51.3

41.1

57

71.2

61.4

51.3

41.1

* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

COOLING CAPACITY - COIL ONLY

*

Model

Rated

CFM

Entering Air °F

(Wet Bulb)

MBH @ EVAPORATOR TEMPERATURE AND

CORRESPONDING PRESSURE °F / PSIG

35/61.5

40/68.5

45/76.0

50/84.0

HC18A

600

72

26.4

24.0

21.5

18.6

67

24.3

22.0

19.4

16.8

62

20.0

17.7

15.3

12.9

57

16.1

14.0

11.8

9.2

HC30A

1000

72

42.7

38.9

34.7

30.6

67

34.3

30.3

26.5

22.5

62

26.7

22.5

24.5

19.8

57

22.9

21.2

19.6

18.3

HC36B

1200

72

73.4

63.1

52.5

41.5

67

58.8

49.3

40.2

30.7

62

45.8

36.4

29.7

24.8

57

39.3

34.4

28.1

23.2

HC42C

1400

72

84.9

73.0

60.1

48.1

67

68.0

58.9

46.5

35.6

62

53.1

42.2

34.4

28.8

57

45.5

40.0

32.0

26.7

HC60D

1800

72

112.8

95.0

77.0

58.4

67

90.3

74.5

58.8

43.1

62

70.3

55.1

43.4

34.9

57

60.4

52.1

40.4

31.9

* See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.

APPLICATION FACTOR-RATED CFM VS. ACTUAL CFM

% OF RATED AIR FLOW 80% 90% RATED CFM 110% 120%

CAPACITY FACTOR

0.96 0.98

1.00

1.02

1.03

Entering Air Temperature Limits

Wet Bulb Temp. ºF

Dry Bulb Temp. ºF

Min.

Max.

Min.

Max.

57

72

65

95