York SUNLINE K4EU120A50A User Manual
Page 8

8
Unitary Products Group
550.39-N4YI
KEU090 - SUPPLY AIR BLOWER PERFORMANCE
1
- (CFM)
BLOWER
SPEED
RPM
AIRFLOW
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(KW)
ESP2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW
2400 CFM
2700 CFM
3000 CFM
3300 CFM
3600CFM
600
0.35
0.62
0.59
0.26
0.70
0.66
0.13
0.78
0.73
-
-
-
-
-
-
655
0.49
0.70
0.66
0.41
0.78
0.72
0.30
0.87
0.82
0.07
0.96
0.90
-
-
-
700
0.60
0.77
0.73
053
0.85
0.80
043
0.95
0.89
0.29
1.06
0.99
0.12
1.17
1.09
800
0.92
0.97
0.90
0.85
1.06
0.99
0.77
1.18
1.10
0.65
1.30
1.21
0.49
1.42
1.32
880
1.18
1.11
1.04
1.11
1.24
1.16
1.03
1.37
1.28
0.91
1.50
1.38
0.77
1.64
1.53
900
1.24
1.15
1.07
1.18
1.28
1.19
1.10
1.42
1.32
0.98
1.55
1.43
0.84-
1.70
1.57
1000
1.58
1.35
1.26
1.53
1.48
1.38
1.46
1.63
1.48
1.37
1.81
1.65
1.24
2.02
1.85
KEU090 - SUPPLY AIR BLOWER PERFORMANCE
1
- (m
3
/s)
BLOWER
SPEED
RPM
AIRFLOW
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
1.1 m
3
/s
1.3 m
3
/s
1.4 m
3
/s
1.6 m
3
/s
1.7 m
3
/s
600
87
0.46
0.59
64
0.52
0.66
32
0.45
0.73
-
-
-
-
-
-
655
122
0.52
0.66
102
0.58
0.72
74
0.65
0.82
17
0.72
0.90
-
-
-
700
149
0.57
0.73
131
0.63
0.80
107
0.71
0.89
72
0.79
0.99
30
0.87
1.09
800
228
0.72
0.90
211
0.79
0.99
191
0.88
1.10
161
0.97
1.21
122
1.06
1.32
880
293
0.83
1.04
275
0.92
1.16
255
1.02
1.28
226
1.12
1.38
191
1.22
1.53
900
308
0.86
1.07
293
0.95
1.19
273
1.06
1.32
243
1.15
1.43
208
1.27
1.57
1000
392
1.01
1.26
379
1.10
1.38
362
1.21
1.48
340
1.35
1.65
308
1.50
1.85
KEU120- SUPPLY AIR BLOWER PERFORMANCE
1
(CFM)
BLOWE
R
SPEED
RPM
AIRFLOW
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
ESP
2
(IWG)
OUTPUT
(BHP)
INPUT
(kW)
3200
3600
4000
4400
4800
700
0.49
1.01
0.94
0.34
1.17
1.09
0.14
1.33
1.24
-
-
-
-
-
-
800
0.84
1.25
1.16
0.71
1.42
1.32
0.53
1.60
1.48
0.30
1.80
1.64
-
-
-
900
1.18
1.48
1.38
1.06
1.70
1.57
0.91
1.92
1.75
0.70
2.18
1.99
0.43
2.45
2.24
950
1.37
1.61
1.50
1.26
1.86
1.71
1.11
2.12
1.95
0.90
2.39
2.18
0.65
2.67
2.44
1000
1.56
1.75
1.62
1.46
2.02
1.85
1.32
2.30
2.10
1.13
2.60
2.38
0.87
2.90
2.65
KEU120 - SUPPPLY AIR BLOWER PERFORMANCE
1
(m
3
/s)
BLOWE
R
SPEED
RPM
AIRFLOW
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
ESP
2
(Pa)
OUTPUT
(kW)
INPUT
(kW)
1.5 m
3
/s
1.7m
3
/s
1.9 m
3
/s
2.0 m
3
/s
2.3 m
3
/s
700
122
0.75
0.94
84
0.87
1.09
35
0.99
1.24
-
-
-
-
-
-
800
208
0.93
1.16
176
1.05
1.32
131
1.19
1.48
74
1034
1.64
-
-
-
900
293
1.10
1.38
263
1.27
1.57
226
1.43
1.75
174
1.62
1.99
107
1.83
2.24
950
340
1.20
1.50
312
1.39
1.71
275
1.58
1.95
223
1.78
2.18
161
1.99
2.44
1000
387
1.30
1.62
362
1.50
1.85
327
1.71
2.10
280
1.94
2.38
216
2.16
2.65
1
Unit resistance is based on a wet evaporator coil and clean filters.
2
Available static pressure in IWG (Pa) to overcome the resistance of the duct system and any accessories added to the unit. Refer to Table 6 for the resistance of these
accessories and to Table 7 for additional motor and drive data
NOTE: Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device.
LEGEND:
TABLE 4 - BLOWER PERFORMANCE
RPM range for the standard factory-mounted drive com-
ponents.
Exceeds the BHP limitation of the standard
factory-mounted blower motor