Installation – York SUNLINE K4EU120A50A User Manual

Page 3

background image

carrier's agent should be made in writing. See Local Dis-
tributor for additional information.

LIMITATIONS

These units must be installed in accordance with applicable na-
tional, local and municipal safety codes.

If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's ex-
pense. Refer to Table 1 for Unit Application Data.

LOCATION

These blower units are not designed for outdoor installation.
They must be located within the building structure, either inside
or outside the conditioned space.

These Evaporator Blower sections allow for vertical or horizon-
tal installation in any area offering proper electrical supply, duct

and drain connections.

They may be installed either with ductwork or matching plenum
and inlet grille.

The unit should be located as close to the condensing unit as
practical and positioned to minimize bends in the refrigerant
piping.

Units being installed vertically or horizontally can be set directly
on a floor or platform, or they can be supported by metal or
wooden beams.

Units being installed horizontally can be suspended from
above. Four

3

8

" (9.5mm) weld nuts are provided in the unit

frame to accommodate hanger rods. Knockouts must be re-
moved from the unit panels to expose these weld nuts. Refer to
Figure 1 for their location and the individual load on each
hanger rod.

WARNING: Be careful when attaching the hanger rods. They

must not be allowed to turn or slip.

Unitary Products Group

3

550.39-N4YI

MODEL

Power
Supply

Voltage

Variation*

Supply Air Range

CFM/m

3

/s

Entering Air Temperature, °F(°C)

Cooling-db/wb

Heating-db

Min.

Max.

Min.

Max.

Min.

Max.

Min.

Max.

KEU090

380/415-3-50

342

457

2400 / 1.3

3600 / 1.7

68/57(20/14) 95/72(18/22)

40(4.4)

77(25)

KEU120

380/415-3-50

342

457

3200 / 1.5

4800 / 2.3

65/57(20/14) 95/72(18/22)

40(4.4)

77(25)

TABLE 1 - UNIT APPLICATION DATA

* Utilization Range “A” in accordance with ARI Standard 110.

INSTALLATION

(66.7)

.

44-7/8 (1140)

(25.7)

(1251) 49-1/4

(35)

1-3/8

FIG. 1 - UNIT SUSPENSION MOUNTING (Horizontal)

Model

Center of Gravity

Dimensions, (In./mm)

Weight Distribution

(lbs/kg)

A

B

W1

W2

W3

W4

TOTAL

KEU090

26

1

4

/ 667

23

3

4

/ 603

85 /38.5

93 / 42.2

70 / 32

77 / 34.9

325 / 147.4

KEU120

26

5

8

/ 676

24

1

8

/ 613

85 /38.5

93 / 42.2

70 / 32

80 / 36.2

330 / 149.7