User Settings
975-0307-01-01
3–33
Generator Menu Items:
“Starter Cool Down”
1s to 250s (increments of 1s)
60s
“Gen Cool Down”
0s to 90 s (increments of 1s)
30s
“Max Run Time”
0hours–24 hours
8hours
“Exercise Per”
0days (Off)–250days
21days
“Exercise Dur”
1min–250min
30min
“Exercise Time”
12:00AM–11:59PM (12-hour clock)
00:00–23:59 (24-hour clock)
9:00AM (12-hour clock)
9:00 (24-hour clock)
“Relay3”
Preheat, WrmupCoolDn, Preheat
SDByp, NotUsed
NotUsed
“Gen Run Hold
Time”
0.5s to 20s (increments of 1s)
0.5s
“Crank Delay”
0s to 60s (increments of 1s)
0s
“Crank Time”
0s to 250s (increments of 1s)
30s
“Crank Retry Time”
0s to 250s (increments of 1s)
40s
“Preheat Time”
0s to 250s (increments of 1s)
0s
“Gen Start Tries”
1 to 10
3
Multi-Unit Configuration:
“Dev Name”
1-15 characters
XW AGS
“Dev Number”
00 to 31
00
Connections:
“DC Conn”
None, HouseBatt1 to 6,
StartBatt1 to 6
HouseBatt1
“AC In”
None, Grid1to 10, Gen1 to 10
Grid1
“AC Out”
None, ACLoad1 to 10
ACLoad1
“Generator”
Gen1 to 10
Gen1
Table 3-3 Generator Configuration Settings, Values, Defaults, and User Settings
Setting
Values
Default
User
Setting