Electrical specifications – Xantrex Technology XW User Manual
Page 102

Specifications
A–2
975-0307-01-01
Electrical Specifications
*Limited to Class 2 levels (100 VA) as in Chapter 2, page 2–5.
Nominal input network voltage
15 Vdc
Maximum operating current
200 mA @ nominal
input network voltage
Relay contact voltage rating
12 Vdc, 30 Vdc max.*
Maximum relay contact current
5 A DC*
Nominal 12/24 V thermostat input voltage
12 Vdc/24 Vdc* = On
Minimum 12/24 V thermostat input voltage
9.5 Vdc*
Maximum 12/24 V thermostat input voltage
30 Vdc*
Typical 12/24 V thermostat input current
14.6 mA @ 12 V
Nominal 12/24 V generator running B+ voltage
12 Vdc/24 Vdc*= On
Minimum 12/24 V generator running B+ voltage
9.5 Vdc*
Maximum 12/24 V generator running B+ voltage
30 Vdc*
Typical 12/24 V generator running B+ current
14.6 mA @ 12 V
Communication physical layer
2, CAN
Communication protocol
Xanbus
Maximum cable length
130 ft. (40 m)