York F*FP User Manual
Page 11

295421-YTG-B-0707
Unitary Products Group
11
FIELD WIRING CONNECTION - COOLING ONLY
FIELD WIRING CONNECTION - WITH HEATER KIT
ELECTRICAL DATA - 3
∅ - (SINGLE SOURCE POWERSUPPLY) - COPPER WIRE
Models
Heater Models
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
1
Amps
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
75°C Wire Size - AWG
208V
240V
208V
240V
208V
240V
F4FP024H06T2*
2HK06501025B
41.2
46.5
45
50
8
8
F4FP030H06T2*
2HK06501025B
42.2
47.4
45
50
8
8
2HK06501525B
42.2
47.4
45
50
8
8
F4FP036H06T2*
2HK06501025B
43.1
48.2
45
50
8
8
2HK06501525B
43.1
48.2
45
50
8
8
F4FP040H06T2*
2HK06501025B
42.2
47.4
45
50
8
8
2HK06501525B
42.2
47.4
45
50
8
8
F4FP042H06T2*
2HK06501025B
44.2
49.1
45
50
8
8
2HK06501525B
44.2
49.1
45
50
8
8
F4FP045H06T2*
2HK06501025B
42.8
47.9
45
50
8
8
2HK06501525B
42.8
47.9
45
50
8
8
F5FP048H06T2*
2HK06501025B
48.3
53.9
50
60
8
6
2HK06501525B
48.3
53.9
50
60
8
6
F5FP060H06T2*
2HK06501025B
48.3
53.9
50
60
8
6
2HK06501525B
48.3
53.9
50
60
8
6
F4FV060H06T2*
2HK06501025B
48.6
52.9
50
60
8
6
2HK06501525B
48.6
52.9
50
60
8
6