York DFAH User Manual
Page 25

107272-UIM-B-1105
Unitary Products Group
25
APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW
Example: For a 84,000 BTUH (38.06 kW) furnace with 1 return open-
ings and operating on high-speed blower, it is found that total system
static is 0.30” w.c. (0.075 kPa). To determine the system airflow, com-
plete the following steps:
Obtain the airflow values at 0.10 w.c. (125 Pa) & 0.20 w.c. (150 Pa)
ESP.
Airflow @ 0.10”: 1175 CFM (60.17 m
3
/min)
Airflow @ 0.20”: 1110 CFM (57.62 m
3
/min)
Subtract the airflow @ 0.10 w.c. (125 Pa) from the airflow @ 0.20 w.c.
(150 Pa) to obtain airflow difference.
1175 - 1110 = -65 CFM (2.55 m
3
/min)
Subtract the total system static from 0.10 w.c. (125 Pa) and divide this
difference by the difference in ESP values in the table, 0.20 w.c.
(150 Pa) - 0.10 w.c. (125 Pa), to obtain a percentage.
(0.30 - 0.10) / (0.20 - 0.10) = 0.5
Multiply percentage by airflow difference to obtain airflow reduction.
(0.5) X (-65) = -32.5
Subtract airflow reduction value to airflow @ 0.10 w.c. (125 Pa) to
obtain actual airflow @ 0.30 wc (144 Pa) ESP.
1050 - 32.5 = 1017.5
FINAL PROCEDURE
Install Furnace Doors
Install the lower door first by sliding the bottom of the door down until
the tabs on the casing base engage the slots in the bottom door end
cap. Then push the top of the lower door in until the door clips snap into
place. Install the upper door in a similar manner, first engaging the slots
in the top of the upper door on the tabs on the casing top. Then snap
the bottom of the upper door into place against the casing.
Finish and Trim
Alcove and Closet Installations may now be finished and trimmed as
necessary.
TABLE 14: Blower Performance CFM
BLOWER PERFORMANCE CFM - DFAA066
FACTORY EQUIPPED WITH STANDARD BLOWERS AND FILTERS
EXTERNAL STATIC PRESSURE, INCHES WC (kPa)
Blower Speed
BTU/H (kW)
Input / Output
CFM
(m
3
/ min)
0.1 (0.025)
0.2 (0.050)
0.3 (0.075)
0.4 (0.099)
0.5 (0.124)
cfm
cm/m
cfm
cm/m
cfm
cm/m
cfm
cm/m
cfm
cm/m
Single Speed - No Coil
66(19.34) / 53(15.55) 1050(29.73)
1175
33.3
1110
31.4
1050
29.7
1000
28.3
950
26.9
Single Speed - With Dry Coil 66(19.34) / 53(15.55) 1050(29.73)
1125
31.9
1070
30.3
1020
28.9
960
27.2
910
25.8
BLOWER PERFORMANCE CFM - DFAA084
EXTERNAL STATIC PRESSURE, INCHES WC (kPa)
Blower Speed
BTU/H (kW)
Input / Output
CFM
(m
3
/ min)
0.1 (0.025)
0.2 (0.050)
0.3 (0.075)
0.4 (0.099)
0.5 (0.124)
cfm
cm/m
cfm
cm/m
cfm
cm/m
cfm
cm/m
cfm
cm/m
Single Speed - No Coil
84(24.62) / 67(19.63) 1250(35.39)
1370
38.8
1305
37.0
1245
35.3
1175
33.3
1100
31.1
Single Speed - With Dry Coil 84(24.62) / 67(19.63) 1250(35.39)
1265
35.8
1195
33.8
1120
31.7
1045
29.6
1015
28.7
BLOWER PERFORMANCE CFM - DFAH066
EXTERNAL STATIC PRESSURE, INCHES WC (kPa)
Blower Speed
BTU/H (kW)
Input / Output
CFM
(m
3
/ min)
0.1 (0.025)
0.2 (0.050)
0.3 (0.075)
0.4 (0.099)
0.5 (0.124)
cfm
cm/m
cfm
cm/m
cfm
cm/m
cfm
cm/m
cfm
cm/m
Single Speed - No Coil
66(19.34) / 53(15.55 1050(29.73)
1155
32.7
1111
31.5
1055
29.9
995
28.2
920
26.1
BLOWER PERFORMANCE CFM - DFAH084
EXTERNAL STATIC PRESSURE, INCHES WC (kPa)
Blower Speed
BTU/H (kW)
Input / Output
CFM
(m
3
/ min)
0.1 (0.025)
0.2 (0.050)
0.3 (0.075)
0.4 (0.099)
0.5 (0.124)
cfm
cm/m
cfm
cm/m
cfm
cm/m
cfm
cm/m
cfm
cm/m
Single Speed - No Coil
84(24.62) / 67(19.63) 1250(35.39)
1127
31.9
1062
30.1
1005
28.5
952
27.0
887
25.1
NOTES:
1. Airflow expressed in standard cubic feet per minute (cfm) and in cubic meters per minute (cm/m)
2. Return air is through louvered filter door only.
3. Motor voltage at 115V