beautypg.com

York SUNLINE 2000 B2CH180 User Manual

Page 7

background image

035-18895-000-A-0902

Unitary Products Group

7

WEIGHTS (kg. / lbs.)

BASIC

UNIT

180

948 / 2091

OPTIONS

Economizer

73 / 160

Motorized Damper

68 / 150

Electric
Heater

18 kW

11 / 25

36kW

14 / 30

54 kW

16 / 35

72 kW

18 / 40

ACCESSORIES

Roof Curb

180

79 / 175

Barometric Damper

20 / 45

Wood
Skid*

180

91 / 200

*

Allows handling of unit using 2286mm (90")
long forks.

COMPONENT DESCRIPTION

UNIT SIZE

180

SUPPLY AIR

BLOWER

CENTRIFUGAL BLOWER

DIA. x WD. (mm)

381 x 381

DIA. x WD. (in.)

15 x 15

FAN MOTOR

kW / HP

3.0 / 4

INDOOR

COIL

ROWS DEEP

4

FINS PER INCH

13

FACE AREA

m

2

/ Ft.

2

1.45 / 15.5

OUTDOOR

FANS

(Two Per Unit)

PROPELLER DIA.

mm / in.

762 / 30 ea.

FAN MOTOR

kW / HP

0.7 / 1 ea.

NOMINAL AIRFLOW

m

3

/s

2.83 ea.

CFM

6000

OUTDOOR

COIL

ROWS DEEP

3

FINS PER INCH

15

FACE AREA

m

2

/ Ft.

2

3.35 / 36.0

COMPRESSOR

(Qty. Per Unit)

SCROLL (6.5 TON NOMINAL CAPACITY)

2

AIR

FILTERS

(SEE NOTE)

QUANTITY PER UNIT

457 x 610 x 51 (mm)

5

18 x 24 x 2 (in.)

TOTAL FACE AREA

m

2

/ Ft.

2

1.40 / 15.0

CHARGE

REFRIGERANT 22

SYS. #1 (kg. / lbs.)

9.5 / 21.0

SYS. #2 (kg. / lbs.)

9.5 / 21.0

NOTE: Filter racks are adapted to accept 25mm (1") or 51mm (2") filters.

TABLE 3 - PHYSICAL DATA

FIG. 6 - ENTHALPY SETPOINT ADJUSTMENT