Electrical data, Basic unit (belt-drive) – York SUNLINE 2000 48 User Manual
Page 13
036-21564-002-A-0404
Unitary Products Group
13
ELECTRICAL DATA
-
Basic Unit (Belt-Drive)
MODEL
BCH
POWER SUP-
PLY
VOLTAGE
LIMITATIONS
(SEE NOTE 1)
COMPRESSOR
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
(SEE NOTE 2)
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN.
MAX.
RLA
LRA
036
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
19.0
11.9
5.9
4.8
105
85
42
34
1.7
1.7
1.0
1.0
5.3
5.3
3.1
3.1
34.1
21.9
11.5
11.1
50
30
15
15
50
30
15
15
048
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
25.0
14.7
7.7
6.4
105
130
64
52
2.3
2.3
1.4
1.4
8.6
5.2
2.6
2.0
38.6
25.9
13.6
11.4
60
40
20
15
60
40
20
15
060
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
32.1
19.3
10.0
7.9
169
123
62
50
2.3
2.3
1.4
1.4
8.6
6.0
3.0
2.4
51.4
32.4
16.9
13.7
80
50
25
20
80
50
25
20
NOTES:
1. Utilization Range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.
MODEL
BCH
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
BREAKER
AMPS
KW
STAGES
TOTAL
AMPS
036
208-1-60
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
8.6
4.0
5.6
8.0
11.9
15.9
1
1
1
2
2
19.1
27.1
38.3
57.4
76.6
58.0
67.9
81.9
105.8
129.7
70
80
90
110
150
70
80
90
110
150
230-1-60
2CE04500506
2CE04500706
2CE04501006
2CE04501506
2CE04502006
8.6
5.3
7.5
10.6
15.9
21.2
1
1
1
2
2
22.1
31.2
44.2
66.2
88.3
61.7
73.1
89.3
116.9
144.5
70
80
90
125
150
70
80
90
125
150
208-3-60
2CE04500525*
2CE04500725*
2CE04501025
2CE04501525
2CE04502025
5.3
4.0
5.6
8.0
11.9
15.9
1
1
1
2
2
11.0
15.6
22.1
33.1
44.2
35.7
41.4
49.5
63.3
77.1
40
45
50
70
80
40
45
50
70
80
230-3-60
2CE04500525*
2CE04500725*
2CE04501025
2CE04501525
2CE04502025
5.3
5.3
7.5
10.6
15.9
21.2
1
1
1
2
2
12.7
18.0
25.5
38.2
51.0
37.8
44.4
53.7
69.7
85.6
45
50
60
70
90
45
50
60
70
90
460-3-60
2CE04500746*
2CE04501046*
2CE04501546*
2CE04502046*
3.1
6.8
10.1
13.6
19.5
1
1
1
2
8.2
12.1
16.4
23.5
21.7
26.7
31.9
40.8
25
30
35
45
25
30
35
45
575-3-60
2CE04501058
2CE04501558
2CE04502058
3.1
10.6
15.9
21.2
1
1
1
10.2
15.3
20.4
16.6
23.0
29.4
20
25
30
20
25
30
1
Dual element, time delay type
2
Standard circuit breakers may be used in Canada and on applications
over 60 amps where the heaters are separately fused.
*
These electric heaters DO NOT include a fuse box. If a fuse box is
required to meet a local code ((eg., Chicago), the following fuse
block accessories are available for field installation.
ELECTRICAL DATA
-
Heat Pump with Supplemental Electric Heat (Belt-Drive)
Electric Heat
Correction
Factors
Nominal Voltage
Voltage
KW Cap
Multipier
208
208
1.00
240
230
0.92
480
460
0.92
600
575
0.92
Fuse Block
2FB04700425
208/240 Volts
2FB04700546
460 Volts