beautypg.com

Dimensions – ycas0300 - 0330 (si), Dimensions – York MILLENNIUM 28971AR User Manual

Page 62

background image

YORK INTERNATIONAL

62

Dimensions –

YCAS0300 - 0330 (SI)

All dimensions are in mm
unless otherwise noted.

NOTES:

1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,

reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres-
sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control
panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be
higher than the unit.

2331

CONTROL
TRANSFORMER
SERVICE SWITCH

112 (EDGE OF
UNIT TO COOLER
CONNECTION)

C

511

C

B

B

OPTIONS PANEL

MICRO-COMPUTER
CONTROL CENTER

VIEW A-A

LD03983

CONTROL ENTRY
(12) 22
CONDUIT K.O.'S

229

VIEW B-B

711

51 TYP.

51

120

305

178

CONTROL
OPENING
(229 HIGH)

51

POWER
OPENING
(533 HIGH)

1067

800

191

VIEW C-C

LD03984