Dimensions – ycas0300 - 0330 (si), Dimensions – York MILLENNIUM 28971AR User Manual
Page 62
YORK INTERNATIONAL
62
Dimensions –
YCAS0300 - 0330 (SI)
All dimensions are in mm
unless otherwise noted.
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres-
sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control
panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be
higher than the unit.
2331
CONTROL
TRANSFORMER
SERVICE SWITCH
112 (EDGE OF
UNIT TO COOLER
CONNECTION)
C
511
C
B
B
OPTIONS PANEL
MICRO-COMPUTER
CONTROL CENTER
VIEW A-A
LD03983
CONTROL ENTRY
(12) 22
CONDUIT K.O.'S
229
VIEW B-B
711
51 TYP.
51
120
305
178
CONTROL
OPENING
(229 HIGH)
51
POWER
OPENING
(533 HIGH)
1067
800
191
VIEW C-C
LD03984