beautypg.com

Temperature and flows, Si units) – York MILLENNIUM 28971AR User Manual

Page 11

background image

YORK INTERNATIONAL

FORM 201.18-EG1

11

TEMPERATURE AND FLOWS

(SI Units)

MODEL

LEAVING WATER

COOLER FLOW

AIR ON

NUMBER

TEMPERATURE (°C)

(L/S)

3

CONDENSER (°C)

YCAS

MIN.

1

MAX.

2

MIN.

MAX.

MIN.

MAX

0090EC

4.4

12.8

7.0

38.0

-17.7

51.7

0100EC

4.4

12.8

8.0

38.0

-17.7

51.7

0110EC

4.4

12.8

8.0

38.0

-17.7

51.7

0120EC

4.4

12.8

8.0

38.0

-17.7

51.7

0130EC

4.4

12.8

9.3

37.8

-17.7

51.7

0140EC

4.4

12.8

10.7

37.8

-17.7

51.7

0150EC

4.4

12.8

11.5

44.2

-17.7

51.7

0160EC

4.4

12.8

11.9

47.1

-17.7

51.7

0170EC

4.4

12.8

12.8

47.1

-17.7

51.7

0180EC

4.4

12.8

13.8

47.1

-17.7

51.7

0200EC

4.4

12.8

14.4

47.1

-17.7

51.7

0210EC

4.4

12.8

15.6

47.1

-17.7

51.7

0230EC

4.4

12.8

17.2

47.1

-17.7

51.7

0250EC

4.4

12.8

14.0

50.0

-17.7

51.7

0270EC

4.4

12.8

14.0

50.0

-17.7

51.7

0300EC

4.4

12.8

16.0

50.0

-17.7

51.7

0330EC

4.4

12.8

16.0

50.0

-17.7

51.7

0360EC

4.4

12.8

19.0

67.0

-17.7

51.7

0400EC

4.4

12.8

21.0

67.0

-17.7

51.7

0440EC

4.4

12.8

21.0

67.0

-17.7

51.7

NOTES:

1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.

2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK office for application guidelines.

3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.