Temperature and flows, Si units) – York MILLENNIUM 28971AR User Manual
Page 11
YORK INTERNATIONAL
FORM 201.18-EG1
11
TEMPERATURE AND FLOWS
(SI Units)
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (°C)
(L/S)
3
CONDENSER (°C)
YCAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0090EC
4.4
12.8
7.0
38.0
-17.7
51.7
0100EC
4.4
12.8
8.0
38.0
-17.7
51.7
0110EC
4.4
12.8
8.0
38.0
-17.7
51.7
0120EC
4.4
12.8
8.0
38.0
-17.7
51.7
0130EC
4.4
12.8
9.3
37.8
-17.7
51.7
0140EC
4.4
12.8
10.7
37.8
-17.7
51.7
0150EC
4.4
12.8
11.5
44.2
-17.7
51.7
0160EC
4.4
12.8
11.9
47.1
-17.7
51.7
0170EC
4.4
12.8
12.8
47.1
-17.7
51.7
0180EC
4.4
12.8
13.8
47.1
-17.7
51.7
0200EC
4.4
12.8
14.4
47.1
-17.7
51.7
0210EC
4.4
12.8
15.6
47.1
-17.7
51.7
0230EC
4.4
12.8
17.2
47.1
-17.7
51.7
0250EC
4.4
12.8
14.0
50.0
-17.7
51.7
0270EC
4.4
12.8
14.0
50.0
-17.7
51.7
0300EC
4.4
12.8
16.0
50.0
-17.7
51.7
0330EC
4.4
12.8
16.0
50.0
-17.7
51.7
0360EC
4.4
12.8
19.0
67.0
-17.7
51.7
0400EC
4.4
12.8
21.0
67.0
-17.7
51.7
0440EC
4.4
12.8
21.0
67.0
-17.7
51.7
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.