Ratings, English units, Model ycas0440ec – York MILLENNIUM 28971AR User Manual
Page 26: Model ycas0400ec
YORK INTERNATIONAL
26
Ratings –
English Units
MODEL YCAS0440EC
(IPLV = 14.9)
40.0
426.4
347.8
13.5 417.2 375.0
12.3
409.0
404.6
11.2
401.7 436.8 10.3
395.4
471.4
9.4
42.0
440.4
351.7
13.8 430.7 379.1
12.6
422.1
409.0
11.5
414.5 441.5 10.5
407.7
476.6
9.6
44.0
454.7
355.5
14.1 444.6 383.1
12.8
435.6
413.3
11.7
427.5 446.2 10.7
420.4
481.7
9.8
45.0
462.0
357.4
14.2 451.7 385.1
13.0
442.4
415.4
11.9
434.2 448.5 10.8
426.9
484.2
9.9
46.0
469.3
359.2
14.4 458.8 387.0
13.1
449.3
417.5
12.0
440.9 450.8 10.9
433.4
486.8 10.0
48.0
484.2
362.8
14.7 473.2 390.9
13.4
463.3
421.7
12.2
454.5 455.4 11.2
446.7
491.9 10.2
50.0
499.5
366.4
15.0 488.0 394.7
13.7
477.7
425.9
12.5
468.5 460.0 11.4
460.3
497.0 10.4
52.0
515.0
369.9
15.4 503.1 398.5
14.0
492.3
430.1
12.8
482.7 464.6 11.7
474.1
502.2 10.6
55.0
538.8
375.2
15.9 526.2 404.3
14.5
514.8
436.4
13.2
504.6 471.7 12.0
495.5
510.1
11.0
40.0
414.1
332.0
13.6 400.5 353.4
12.4
387.0
376.3
11.4
374.9 401.2 10.4
363.3
427.5
9.5
42.0
428.3
337.7
13.9 414.2 359.5
12.7
400.8
383.0
11.6
388.0 408.2 10.6
375.5
435.0
9.6
44.0
442.6
343.3
14.1 428.2 365.5
12.9
414.3
389.5
11.8
401.2 415.2 10.8
388.7
442.6
9.8
45.0
449.8
346.0
14.3 435.1 368.5
13.0
421.2
392.7
11.9
407.8 418.6 10.8
395.2
446.4
9.9
46.0
457.1
348.7
14.4 442.2 371.4
13.1
428.1
395.9
12.0
414.5 422.1 10.9
401.7
450.2 10.0
48.0
471.7
354.1
14.6 456.5 377.3
13.4
441.9
402.3
12.2
428.1 429.1 11.1
414.9
457.7 10.2
50.0
486.5
359.5
14.9 470.9 383.2
13.6
455.9
408.6
12.4
441.8 436.0 11.3
428.3
465.3 10.3
52.0
501.5
364.8
15.1 485.5 389.0
13.8
470.2
415.1
12.6
455.6 443.1 11.5
441.8
473.0 10.5
55.0
524.2
372.7
15.5 507.6 397.7
14.2
491.8
424.7
12.9
476.7 453.7 11.8
462.4
484.7 10.7
MODEL YCAS0400EC
(IPLV = 14.5)
LCWT
AIR TEMPERATURE ON CONDENSER (°F)
(°F)
75
80
85
90
95
TONS
kW
EER
TONS
kW
EER
TONS
kW
EER
TONS
kW
EER
TONS
kW
EER
NOTES:
1. kW
= Compressor Input Power
2. EER
= Chiller EER (includes power from compressors, fans, and control panel’s 0.8 KW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings based on 2.4 GPM cooler water per ton