a) Water boiler(s) controls furnished:

1) High temperature limit setting to be 140 – 240 degrees.
2) Combination

pressure-temperature gauge with dial clearly marked

and easy to read, installed with well for removal without draining the
boiler.

3) ASME certified pressure relief valve, set to relieve at 30 PSIG.

Optional relief valves available up to and including maximum
allowable pressure. Side outlet discharge type; contractor to pipe
outlet to floor drain or near floor, avoiding any area where freezing
could occur.

4) Integrated spark module for blower control with indicator lights for

easy troubleshooting.

E. Boiler

Manuals:

1. Boiler, gas control and user’s information manual.
2. Venting supplements and instructions.