Burner specifications and settings, Continued), Table 2 – Weil-McLain RS User Manual

Page 3: Table 3, Burner data — natural gas — general, Gas control components and sizes

background image

Burner Specification & Data sheet — Riello Gas Burners

3

Part No. 550-142-025/0508

Burner specifications and settings

(continued)

Burner data — Natural gas — General

Table 2

Boiler

Model

Number

Burner

Input

Positive

Pressure In

Firebox

Standard Burner Model

Designation

Standard

Combustion

Control

Standard

Control System

Burner Motor H.P.

3400 RPM

Standard

Motor Voltage

Inches W.C.

On - Off

LHL/MOD

Note 14

On - Off

LHL/MOD

On - Off

LHL/MOD

On - Off

LHL/MOD

488R

996

.89

RS28/1

RS28/M

LFL 1.335**

00

LHL/MOD

1/2

1/2

120/60/1

120/60/1

488

1010

1.00

RS28/1

RS28/M

LFL 1.335**

00

LHL/MOD

1/2

1/2

120/60/1

120/60/1

588

1357

.89

RS38/1

RS38/M

LFL 1.335**

00

LHL/MOD

1/2

1/2 OR 3/4

120/60/1

120/60/1

688

1703

.72

RS50/M

LFL 1.335**

LHL/MOD

3/4

120/60/1 or 3 phase*

788

2049

.65

RS50/M

LFL 1.335**

LHL/MOD

3/4

3 phase*

888

2396

.85

RS70/M

LFL 1.335**

LHL/MOD

1 1/2

3 phase*

988R

2482

.80

RS70/M

LFL 1.335**

LHL/MOD

1 1/2

3 phase*

988

2713

.80

RS70/M

LFL 1.335**

LHL/MOD

1 1/2

3 phase*

1088R

2887

.82

RS70/M

LFL 1.335**

LHL/MOD

1 1/2

3 phase*

1088

3103

.82

RS100/M

LFL 1.335**

LHL/MOD

2 1/2

3 phase*

1188

3392

.82

RS100/M

LFL 1.335**

LHL/MOD

2 1/2

3 phase*

1288

3753

.81

RS100/M

LFL 1.335**

LHL/MOD

2 1/2

3 phase*

1388

4113

.89

RS100/M

LFL 1.335**

LHL/MOD

2 1/2

3 phase*

1488

4474

.86

RS130/M

LFL 1.335**

LHL/MOD

3

3 phase*

1588

4763

.86

RS130/M

LFL 1.335**

LHL/MOD

3

3 phase*

1688R

4979

.863

RS130/M

LFL 1.335**

LHL/MOD

3

3 phase*

1688

5124

.83

RS130/M

LFL 1.335**

LHL/MOD

3

3 phase*

1788

5485

.82

RS130/M

LFL 1.335**

LHL/MOD

3

3 phase*

1888

5845

.85

RS190/M

LFL 1.335**

LHL/MOD

3

3 phase*

*208/60/3, 240/60/3, 480/60/3, 575/60/3, burner motor voltage must be specified

Gas control components and sizes

Table 3

Boiler

Model

Number

Manual

Hand Valve

Low Gas

Pressure Switch

Gas

Pressure Regulator

Operating

Gas Valve

Operating Gas

Valve (with Proof Of

Closure)

Safety

Gas Valve

Manual

Checking Gas Valve

High Gas

Pressure Switch

Inches

Inches

Inches

Inches

Inches

488R – 688

1 1/2

Standard

1 1/2

1 1/2

Optional

1 1/2

1 1/2

Standard

788 – 1188

2

Standard

2

2

Optional

2

2

Standard

1288 – 1688R

2 1/2

Standard

2 1/2

2 1/2

Optional

2 1/2

2 1/2

Standard

1688 – 1888

3

Standard

3

3

Optional

3

3

Standard