beautypg.com

Annual service check list – Weil-McLain WGO User Manual

Page 8

background image

8

The procedures and information on pages 7 through 11 are

intended only for a qualified service technician who has the necessary
equipment to inspect and adjust boiler and burner. A homeowner should
never attempt these procedures. Qualified service technician must read
pages 2 and 3 before proceeding.

Annual Service Check List

Any parts of the boiler furnished by Weil-McLain must be replaced by parts listed in

Weil-McLain Boiler and Repair Parts Book.

Annual Service Call Check List

(follow in order listed below)

D

A
T

E

D

A
T

E

D

A
T

E

D

A
T

E

D

A
T

E

D

A
T

E

D

A
T

E

D

A
T

E

D

A
T

E

D

A
T

E

Comments

1

Check that boiler area is free from
combustible materials, gasoline and other
flammable vapors and liquids.

2

Check for and remove any obstruction to
combustion and ventilation air flow to boiler.

3

Check breeching and chimney or vent for
obstructions, damage, etc. Repair or replace
as necessary.

4

Clean boiler flueways. See page 9.

5

Perform service on relief valve and circulator.
See page 11.

6

Check boiler and piping for leaks and repair if
found. Check for leaks at tankless heater
plate. Tighten nuts only if leaks are found (for
WTGO torque to 20-25 ft.lbs.).

7

Inspect and adjust burner. See burner manual
and:
- change nozzle.
- check ignition electrode settings.
- clean blower housing and wheel.
- make sure blower wheel turns freely.
- oil burner motor if required.
- clean air inlet.
- clean or change fuel filter and strainer.

8

Make sure boiler is filled with water.

9

Start unit and verify combustion settings with
combustion test equipment.
See page 10.

10 Verify operation of all controls on boiler. See

page 11.