Start-up

WGO/WTGO (see Figure 1):

1. If burner does not fire, check for:

Service switch on boiler or additional
switches turned off.
Fuses or breaker switch tripped.
Thermostat set below room temperature.
Fuel valves turned off.
Not enough oil in tank to supply burner.

DANGER

WGO and WTGO Boilers

Figure 1

2. Correct problems found in step #1. If burner

does not fire, press reset button on burner
primary control only once. Repeated presses
will deposit oil in combustion chamber.

Burner must never be fired

when oil is in combustion chamber. Immedi-
ately call qualified service technician.

3. If burner still does not fire, call qualified

service technician.