Technical Data

R

C

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 2. Typical wiring diagram for single transformer single stage systems

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Heat Relay

Fan

Relay

Optional

Optional Jumper for

Single Stage Heat Pump

R

C

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 2. Typical wiring diagram for single transformer single stage systems

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Heat Relay

Fan

Relay

Optional

Optional Jumper for

Single Stage Heat Pump

R

C

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 3. Typical wiring diagram for two transformer single stage systems with NO safety circuits

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Heat Relay

Fan

Relay

Optional

Limit or

Safety

Switches

TWO COMMONS MUST
BE JUMPERED TOGETHER!

HOT

NEUTRAL

120 VAC

24 VAC

CUT AND

TAPE OFF!

If safety circuits are in only one of
the systems, remove the transformer
of the system with

NO safety circuits.

NOTE

Optional Jumper for

Single Stage Heat Pump

R

C

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 3. Typical wiring diagram for two transformer single stage systems with NO safety circuits

TRANSFORMER

(Class II Current Limited)

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Heat Relay

Fan

Relay

Optional

Limit or

Safety

Switches

TWO COMMONS MUST
BE JUMPERED TOGETHER!

HOT

NEUTRAL

120 VAC

24 VAC

CUT AND

TAPE OFF!

If safety circuits are in only one of
the systems, remove the transformer
of the system with

NO safety circuits.

NOTE

Optional Jumper for

Single Stage Heat Pump

R

C

G

W

Figure 4. Typical wiring diagram for two transformer single stage systems with safety circuits in BOTH systems

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Heat

Relay

Fan

Relay

Optional

TWO COMMONS MUST
BE JUMPERED TOGETHER!

24 VAC

120 VAC

HOT

NEUTRAL

THERMOSTAT

SYSTEM

HOT

NEUTRAL

120 VAC

Limit or

Safety

Switches

Limit or

Safety

Switches

Limit or

Safety

Switches

24 VAC

Limit or

Safety

Switches

COMMON

COMMON

Auxiliary

Heating

Transformer

(Class II

Current Limited)

Heat Pump Transformer

(Class II Current Limited)

24 VAC

ACCESSORY

RELAY N.O.

CONTACT

Polarity must be observed. If the HOT side of the
second transformer is jumpered to the COMMON side
of the first transformer a short will be made. Damage
to equipment will occur when power is restored.

NOTE

The accessory relay scheme
is required when safety
circuits exist in both systems.

NOTE

Optional Jumper for

Single Stage Heat Pump

R

C

G

W

Figure 4. Typical wiring diagram for two transformer single stage systems with safety circuits in BOTH systems

Changeover

Relay*

Y

O/B

Compressor

Contactor

* Changeover Relay is energized in COOL when O/B switch is in the “O” position

Changeover Relay is energized in HEAT when O/B switch is in the “B” position

Heat

Relay

Fan

Relay

Optional

TWO COMMONS MUST
BE JUMPERED TOGETHER!

24 VAC

120 VAC

HOT

NEUTRAL

THERMOSTAT

SYSTEM

HOT

NEUTRAL

120 VAC

Limit or

Safety

Switches

Limit or

Safety

Switches

Limit or

Safety

Switches

24 VAC

Limit or

Safety

Switches

COMMON

COMMON

Auxiliary

Heating

Transformer

(Class II

Current Limited)

Heat Pump Transformer

(Class II Current Limited)

24 VAC

ACCESSORY

RELAY N.O.

CONTACT

Polarity must be observed. If the HOT side of the
second transformer is jumpered to the COMMON side
of the first transformer a short will be made. Damage
to equipment will occur when power is restored.

NOTE

The accessory relay scheme
is required when safety
circuits exist in both systems.

NOTE

Optional Jumper for

Single Stage Heat Pump