APPLICATION FIELD WIRING

Oil Valve

Capacitor

GREEN

BLUE

BLACK

BLACK

WH

IT

E

BL

UE

M

BR

O

W

N

AL 1009-1

Burner Fan-Off

Timer

6 12

8

N

1

11

9

3

2

7

Control Box

530 SE/C

YELLOW

BLUE

RED

GREY

L

WH

IT

E

RED

BLACK

W G R B

WH

IT

E

RE

D

BROWN

Ground

FACTORY WIRED

SUB BASE

LIMIT

Switches

SAFETY

Switches

Fuse 15 A

L1

L2

Earth

Ground

WH

IT

E

G

REEN

BLACK

RED

FIELD

WIRING

Motor

4

AIR PRESSURE

SWITCH

10

BLUE

BLUE

BLUE

REMOTE SENSING OF SAFETY LOCKOUT
The SAFETY SWITCH in the 530SE CONTROL BOX is equipped with a contact allowing remote sensing of burner

lockout. The electrical connection is made at terminal 4 (

) on the SUB-BASE.

Should lockout occur the 530SE CONTROL BOX will supply a power source of 120Vac to the connection terminal.

The maximum allowable current draw on this terminal (4) is 1 Amp.

WARNING:

If a neutral or ground lead is attached to this terminal, the CONTROL BOX on the burner will be damaged

should lockout occur.