Burner components – Weil-McLain 800062000-Brn-PO Rie BF5 User Manual
Page 5

3398
2
GB
TECHNICAL DATA
SPECIFICATIONS
BURNER AND MOUNTING FLANGE DIMENSIONS
BURNER COMPONENTS IDENTIFICATION
Fuel
No. 2 Fuel Oil
BF3 Firing rate - Effective Output
0.50 to 0.95 US GPH - 70,000 to 133,000 BTU/h
BF5 Firing rate - Effective Output
0.75 to 1.65 US GPH - 105,000 to 231,000 BTU/h
Voltage (single phase)
120V 60Hz (+ 10% - 15%)
BF3 Absorbed electrical power
192 Watts
BF5 Absorbed electrical power
204 Watts
Motor (rated)
3250 rpm Run Current 2.2 AMP
Capacitor
12.5 Microfarads 260V
Pump pressure
100 to 200 PSI
Primary control
RIELLO 530 SE/C
Ignition transformer
8kV 16mA
Model
A
B
C
D
E
F
BF3
Inches
9 13/16
11 1/4
7 1/2
3 1/2
4 5/8
8 21/32
mm
249
286
193
89
117
220
BF5
Inches
9 13/16
11 1/2
7 1/2
3 1/2
6 5/16
6 13/16
mm
249
292
193
89
160
173
5 9/16”-141mm
7 9/16” - 192 mm
8 1/2” - 216 mm
3
9
/ 16
”
90
mm
60
°
45°
30°
BURNER COMPONENTS
1
Lockout indicator lamp and reset button
2
Primary control
3
Primary control sub-base
4
Pump pressure regulator
5
Post purge timer
6
Air adjustment
7
Capacitor
8
Combustion head
9
Mounting gasket
10
Universal mounting flange
11
Turbolator adjustment screw
12
Coil
13
Bleeder and pressure gauge port
14
Return fuel line port
15
Inlet fuel line port
16
Pump
17
Air pressure switch
D7516
D7515
B
A
E
F
C
D
0
3
D8174
1
2
3
4
5
6
7
15
8
9
10
11
12
13
14
16
17