PER Series 3 Electric-Hydronic Boilers Installation Instructions
60%
70%
80%
90%
100%
200
210
220
230
240
Input Voltage
P
e
rc
e
n
t
o
f
R
a
te
d
C
a
p
a
ci
ty
39601
Ratings
DOE
Required wire sizes and weights
Boiler
model
number
DOE heating
capacity
Boiler input
Number of
elements
Element size
Total
amperes
Volts phase
wire
Wire size
90˚C field
wiring
Boiler
water
content
Approximate
shipping wt.
BTU/Hr
KW
KW
(Note 2)
(Note 3)
Gallons
lbs.
PER-15
51,000
15
3
5
65
240/1/3
4
5.2
215
PER-20
68,000
20
4
5
86
240/1/3
3
5.2
215
PER-25
85,000
25
5
5
107
240/1/3
1
5.2
215
Notes:
1. Provide manual shutoff valves in the system piping at the supply outlet and the return inlet so the boiler can be drained without draining the entire
system.
2. For other than the standard voltages shown, consult Weil-McLain Application Engineering Department.
3. Copper wire (AWG-MCM). Consult national or local electrical code manuals for runs in excess of 50 feet. Do no use aluminum wire.
4. All ratings are based on 240-volt power input. See Figure 1 for percent of boiler capacity when the input voltage is below 240 volts. Gross output
ratings. Piping loss not confined to the heated area should be added to the building loss to determine total heating equipment.
Figure 1
Boiler capacities at various voltages