— Control supplement & Service guide

How to set parameters

Using the boiler display

With the six buttons on the front of the boiler and
the proper code the boiler can be both monitored and
modified using the digital display (Figure 25).

Perform the following steps with the boiler powered
and in a standby condition.

1. On the boiler display in [STBY] mode

2. Press and hold the

button. While holding

the “Step” button press and hold the

button.

Hold both buttons together for several seconds until
“Code” is displayed. Release buttons. “Code” stays
on the display.

3. NOTE: If [CODE] is not displayed after several

seconds release the buttons and press the

button several times to return to [STBY]. Repeat
step two again.

4. Press

the

button once.

5. Adjust the number displayed to [C - 05] by using

the

and

buttons.

6. Press the “Store” button.

The Ultra control module will automati-

cally exit code mode after10 minutes of
no activity.

7. Press the mode button several times until [PARA]

is displayed.

8. Press

the

button several times until [P-XX]

is displayed. The XX represents the parameter that
will be changed. The parameter’s value will then be
displayed.

9. Use the

or

buttons to adjust to the

desired value.

10. Press the

button. Steps 8 through 10 can now

be repeated for additional parameter changes. Or
continue to step 11 to exit.

11. Press the

button until [STBY] is displayed

to exit.

Ultra boiler digital display

&IGURE

2EVISE

.

Tampering with control settings can result in unreliable
operation, with possible severe personal injury, death or
substantial property damage.

This document must only be used by a qualified heating

installer/service technician. Read all instructions, includ-
ing this Addendum, the Ultra Boiler Control Supplement
and the Boiler Manual before installing. Perform steps in
the order given. Failure to comply could result in severe
personal injury, death or substantial property damage.

After making changes to parameters, record the changes

made on the last page of this supplement, and leave a
copy with the boiler for future reference.

Installation must comply with local requirements and

with the National Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 or B149.2 for Canadian
installations.