Burner specifications and settings, Table 2 – Weil-McLain WCR User Manual
Page 3
Burner Specification & Data sheet — Power Flame Gas/Oil Burners — Model WCR
3
Part No. 550-142-029/0508
Burner specifications and settings
(continued)
Gas train components and flame safeguards
Table 2
Boiler
Model
Number
Pressure
Drop Thru
Gas Train
Inches
W.C.
Manifold
Pressure
Inches
W.C.*
Gas Pressure
Required At Gas
Control Inlet
Inches W.C.*
Initial Low Fire
Damper Setting
Inches
Oil Nozzle
(One Per Unit)
Oil Pressures
Psig
Fuel Unit Data Burner-
Motor Driven
3450 Rpm
Min
Max
Top
Bottom
Gph @
100
Psig
Bypass
Oil
System
Brand**
Type
Spray
Angle
Pump
Capacity
Psig
High Fire
Pump
Pressure
Approximate Return
Psig
Type
Gear
Gph
High Fire Low Fire
488R
2.20
2.10
4.10
14.00
M\,
M\,
4.50
No
Delavan
Solid
80°
300
295
—
100-150 B2TA-8850-4
37
488
2.20
2.10
4.30
14.00
M\,
M\,
4.50
No
Delavan
Solid
80°
300
300
—
100-150 B2TA-8850-4
37
588
1.80
2.60
4.40
14.00
1
1
5.50
No
Delavan
Solid
80°
300
300
—
100-150 B2TA-8850-4
37
688
2.70
1.70
4.40
14.00
C\,
C\,
7.00
No
Delavan
Solid
80°
300
300
183
100-150 B2TA-8851-4
43
788
2.50
2.30
4.80
14.00
C\,
C\,
8.50
No
Delavan
Solid
70°
300
300
195
100-150 B2TA-8851-4
43
888
3.90
1.20
5.10
14.00
C\,
C\,
9.50
No
Delavan
Solid
70°***
300
300
210
100-150 B2GA-8852
43
988R
4.60
1.60
6.20
14.00
C\,
C\,
10.00
No
Monarch
PLP
60°
300
300
110
80-100
B2GA-8852
47
988
4.50
1.90
6.40
14.00
C\,
C\,
11.00
No
Delavan
Solid
70°***
300
280
135
80-100
B2GA-8852
47
1088R
4.90
2.00
6.90
14.00
C\,
C\,
12.00
No
Monarch
PLP
60°
300
290
140
80-100
B2GA-8852
47
1088
4.00
2.30
6.30
14.00
C\,
C\,
16.00
Yes
Del. Variflo
BPS
80°
300
225
150
100-150
22R322D
105
1188
3.30
2.10
5.40
14.00
C\,
C\,
(fixed)
14.00
Yes
Del. Variflo
BPS
80°
300
295
140
50-108
22R322D
105
1288
4.10
2.50
6.50
14.00
C\,
C\,
(fixed)
16.00
Yes
Del. Variflo
BPS
80°
300
290
133
50-110
22R322D
105
1388
3.50
2.70
6.20
27.70
C\,
C\,
18.00
Yes
Del. Variflo
BPS
80°
300
244
166
60-108
22R322D
105
1488
4.70
3.60
8.20
27.70
Z\v
Z\v
20.00
Yes
Del. Variflo
BPS
80°
300
280
180
100-150
22R623D
105
1588
5.30
3.90
9.20
27.70
Z\v
Z\v
22.00
Yes
Del. Variflo
BPS
60°
300
290
165
100-150
22R623D
105
1688R
5.80
4.10
10.50
27.70
Z\v
Z\v
22.00
Yes
Del. Variflo
BPS
60°
300
295
175
100-150
22R623D
135
1688
6.20
4.40
10.50
27.70
Z\v
Z\v
22.00
Yes
Del. Variflo
BPS
60°
300
295
155
100-150
22R623D
135
1788
6.50
2.80
9.30
27.70
Z\v
Z\v
24.00
Yes
Hago
BPS
60°
300
300
165
100-150
22R623D
135
1888
7.10
3.20
10.30
27.70
Z\v
Z\v
26.00
Yes
Hago
BPS
60°
300
300
175
100-150
22R623D
135
* Gas pressure shown are for standard gas train arrangement ** Primary manufacturer. For alternate nozzles, contact Power-Flame
*** 70° spray angle standard, 60° or 80° approved and available upon request
Standard Gas Control Components And Sizes In Inches
Boiler Model
Number
Manual Hand
Valve
Low Gas
Pressure
Switch
Gas
Pressure
Regulator
Combination
Gas Valve And
Regulator
Motorized
Operating
Gas Valve
Motorized Operating
Gas Valve
(With Proof Of Closure)
Safety
Gas Valve
Manual
Checking
Gas Valve
High
Gas Pressure
Switch
488R-488
1Z\v
Optional
Optional
1Z\v
Optional
Optional
1Z\v
1Z\v
Optional
588
1Z\v
Optional
Optional
1Z\v
Optional
Optional
1Z\v
1Z\v
Optional
688
1Z\v
Optional
Optional
1Z\v
1Z\v
Optional
*
1Z\v
Optional
788
1Z\x
Optional
Optional
1Z\x
1Z\x
Optional
*
1Z\x
Optional
888
2
Optional
Optional
1Z\x
1Z\x
Optional
*
1Z\x
Optional
988R
2
Optional
2
—
1Z\x
Optional
1Z\x
1Z\x
Optional
988-1088R
2
Standard
2
—
2
Optional
1Z\x
1Z\x
Standard
1088
2
Standard
2
—
2
Optional
2
2
Standard
1188-1588
2
Standard
2
—
2
Optional
2
2
Standard
1688R-1888
2
Standard
2
—
—
2
2
2
Standard
* Combination operating gas valve and regulator also serves as safety gas valve.
Light Oil Control Systems:
17.
FALFS
On-off operation, fixed air, reduced fuel low fire start, high fire run. Single-
position air, two-position oil.
OO
On-off operation, low fire start, high fire run. Single-position air, single-position
oil.
LHO
On-off operation, low fire start, high fire run. Two-position air, two-position oil.
Fixed damper pre-purge on 488-1288, open damper pre-purge on 1388-1888.
LHL
Low-high-low-off firing conditions. Two-position air, two-position oil. Fixed
damper pre-purge on 488-1288. Open damper pre-purge on 1388-1888.
MOD
On-off operation, with proven low fire start and full modulating firing condi-
tions. Proportional motor drives fuel metering valve and combustion air damper
according to the firing conditions. Fixed damper pre-purge on 488-1088R, open
damper pre-purge on 1088-1888.
Gas/Light Oil Control Systems:
18.
OO/FALFS Combines gas and light oil characteristics
listed above.
OO/OO
Combines gas and light oil characteristics
listed above.
LHO/LHO Combines gas and light oil characteristics
listed above. Open damper pre-purge on
1388-1888.
LHL/LHL Combines gas and light oil characteristics
listed above. Open damper pre-purge on
1388-1888.
MOD/MOD Combines gas and light oil characteristics
listed above. Open damper pre-purge on
1388-1888.