Burner Specification & Data sheet — Power Flame Gas/Oil Burners — Model WCR

3

Part No. 550-142-029/0508

Burner specifications and settings

(continued)

Gas train components and flame safeguards

Table 2

Boiler

Model

Number

Pressure

Drop Thru

Gas Train

Inches

W.C.

Manifold
Pressure

Inches

W.C.*

Gas Pressure

Required At Gas

Control Inlet

Inches W.C.*

Initial Low Fire

Damper Setting

Inches

Oil Nozzle

(One Per Unit)

Oil Pressures

Psig

Fuel Unit Data Burner-

Motor Driven

3450 Rpm

Min

Max

Top

Bottom

Gph @

100
Psig

Bypass

Oil

System

Brand**

Type

Spray
Angle

Pump

Capacity

Psig

High Fire

Pump

Pressure

Approximate Return

Psig

Type

Gear

Gph

High Fire Low Fire

488R

2.20

2.10

4.10

14.00

M\,

M\,

4.50

No

Delavan

Solid

80°

300

295

100-150 B2TA-8850-4

37

488

2.20

2.10

4.30

14.00

M\,

M\,

4.50

No

Delavan

Solid

80°

300

300

100-150 B2TA-8850-4

37

588

1.80

2.60

4.40

14.00

1

1

5.50

No

Delavan

Solid

80°

300

300

100-150 B2TA-8850-4

37

688

2.70

1.70

4.40

14.00

C\,

C\,

7.00

No

Delavan

Solid

80°

300

300

183

100-150 B2TA-8851-4

43

788

2.50

2.30

4.80

14.00

C\,

C\,

8.50

No

Delavan

Solid

70°

300

300

195

100-150 B2TA-8851-4

43

888

3.90

1.20

5.10

14.00

C\,

C\,

9.50

No

Delavan

Solid

70°***

300

300

210

100-150 B2GA-8852

43

988R

4.60

1.60

6.20

14.00

C\,

C\,

10.00

No

Monarch

PLP

60°

300

300

110

80-100

B2GA-8852

47

988

4.50

1.90

6.40

14.00

C\,

C\,

11.00

No

Delavan

Solid

70°***

300

280

135

80-100

B2GA-8852

47

1088R

4.90

2.00

6.90

14.00

C\,

C\,

12.00

No

Monarch

PLP

60°

300

290

140

80-100

B2GA-8852

47

1088

4.00

2.30

6.30

14.00

C\,

C\,

16.00

Yes

Del. Variflo

BPS

80°

300

225

150

100-150

22R322D

105

1188

3.30

2.10

5.40

14.00

C\,

C\,

(fixed)

14.00

Yes

Del. Variflo

BPS

80°

300

295

140

50-108

22R322D

105

1288

4.10

2.50

6.50

14.00

C\,

C\,

(fixed)

16.00

Yes

Del. Variflo

BPS

80°

300

290

133

50-110

22R322D

105

1388

3.50

2.70

6.20

27.70

C\,

C\,

18.00

Yes

Del. Variflo

BPS

80°

300

244

166

60-108

22R322D

105

1488

4.70

3.60

8.20

27.70

Z\v

Z\v

20.00

Yes

Del. Variflo

BPS

80°

300

280

180

100-150

22R623D

105

1588

5.30

3.90

9.20

27.70

Z\v

Z\v

22.00

Yes

Del. Variflo

BPS

60°

300

290

165

100-150

22R623D

105

1688R

5.80

4.10

10.50

27.70

Z\v

Z\v

22.00

Yes

Del. Variflo

BPS

60°

300

295

175

100-150

22R623D

135

1688

6.20

4.40

10.50

27.70

Z\v

Z\v

22.00

Yes

Del. Variflo

BPS

60°

300

295

155

100-150

22R623D

135

1788

6.50

2.80

9.30

27.70

Z\v

Z\v

24.00

Yes

Hago

BPS

60°

300

300

165

100-150

22R623D

135

1888

7.10

3.20

10.30

27.70

Z\v

Z\v

26.00

Yes

Hago

BPS

60°

300

300

175

100-150

22R623D

135

* Gas pressure shown are for standard gas train arrangement ** Primary manufacturer. For alternate nozzles, contact Power-Flame

*** 70° spray angle standard, 60° or 80° approved and available upon request

Standard Gas Control Components And Sizes In Inches

Boiler Model

Number

Manual Hand

Valve

Low Gas

Pressure

Switch

Gas

Pressure

Regulator

Combination

Gas Valve And

Regulator

Motorized

Operating

Gas Valve

Motorized Operating

Gas Valve

(With Proof Of Closure)

Safety

Gas Valve

Manual

Checking

Gas Valve

High

Gas Pressure

Switch

488R-488

1Z\v

Optional

Optional

1Z\v

Optional

Optional

1Z\v

1Z\v

Optional

588

1Z\v

Optional

Optional

1Z\v

Optional

Optional

1Z\v

1Z\v

Optional

688

1Z\v

Optional

Optional

1Z\v

1Z\v

Optional

*

1Z\v

Optional

788

1Z\x

Optional

Optional

1Z\x

1Z\x

Optional

*

1Z\x

Optional

888

2

Optional

Optional

1Z\x

1Z\x

Optional

*

1Z\x

Optional

988R

2

Optional

2

1Z\x

Optional

1Z\x

1Z\x

Optional

988-1088R

2

Standard

2

2

Optional

1Z\x

1Z\x

Standard

1088

2

Standard

2

2

Optional

2

2

Standard

1188-1588

2

Standard

2

2

Optional

2

2

Standard

1688R-1888

2

Standard

2

2

2

2

Standard

* Combination operating gas valve and regulator also serves as safety gas valve.

Light Oil Control Systems:

17.

FALFS

On-off operation, fixed air, reduced fuel low fire start, high fire run. Single-
position air, two-position oil.

OO

On-off operation, low fire start, high fire run. Single-position air, single-position
oil.

LHO

On-off operation, low fire start, high fire run. Two-position air, two-position oil.
Fixed damper pre-purge on 488-1288, open damper pre-purge on 1388-1888.

LHL

Low-high-low-off firing conditions. Two-position air, two-position oil. Fixed
damper pre-purge on 488-1288. Open damper pre-purge on 1388-1888.

MOD

On-off operation, with proven low fire start and full modulating firing condi-
tions. Proportional motor drives fuel metering valve and combustion air damper
according to the firing conditions. Fixed damper pre-purge on 488-1088R, open
damper pre-purge on 1088-1888.

Gas/Light Oil Control Systems:

18.

OO/FALFS Combines gas and light oil characteristics

listed above.

OO/OO

Combines gas and light oil characteristics
listed above.

LHO/LHO Combines gas and light oil characteristics

listed above. Open damper pre-purge on
1388-1888.

LHL/LHL Combines gas and light oil characteristics

listed above. Open damper pre-purge on
1388-1888.

MOD/MOD Combines gas and light oil characteristics

listed above. Open damper pre-purge on
1388-1888.