beautypg.com

8 operation and description of instrument function, 1 hart device designation, 2 device data – Varec 4532 User Manual

Page 41: 1 temperature measurement, 1 primary values: vh00 ~ vh09, Operation and description of instrument function, Hart device designation, Device data, Temperature measurement, Primary values: vh00 ~ vh09

background image

Varec, Inc.

31

4532

Operation and Description of Instrument Function

8 Operation and Description of Instrument Function

8.0.1

HART Device designation

HART device code "190":

Device code for temperature measurement function in 4532 ATC only.

8.0.2

Device Data

Tag Number: read and write

Default: HART

A customer specific device identification and control number (or name). Tank name, site

number, or any other ID can be entered.

Assembly Number: read and write

Default: 0

Manufacture control number based on production process.

8.1

Temperature measurement

8.1.1

Primary values: VH00 ~ VH09

VH00 Liquid Temp

Item type: read only

Range: -200°C ~ 240°C

Note!

Display of measured liquid phase average temperature. Liquid level input must be
provided by the 7200 or 7500 Series Radar Tank Gauge (via 4590 TSM) or 6000
Series Servo Tank Gauge in order to calculate true liquid average temperature.

VH01 Gas Temp

Item type: read only

Range: -200°C ~ 240°C

Display of measured gas (vapor) phase average temperature.

Note!

Display of measured gas (vapor) phase average temperature. Liquid level input
must be provided by the 7200 or 7500 Series Radar Tank Gauge (via 4590 TSM) or
6000 Series Servo Tank Gauge in order to calculate true gas average temperature.

VH02 Measured Distance

Item type: read and write

Range: 0mm ~ 99999mm

Display of provided liquid level by connected level gauge. Manual level input is also

available for the purpose of device testing.