Page 4

background image

Proper installation/ducting is extremely
important to ensure maximum
performance. Use a qualified and
trained installer.

DUCTING
• Check with a qualified and

trained installer or local codes
for makeup air requirements, if
any.

• Max. duct run length

o For 300 – 1,200 CFM—50’

(152.4 m)

o For 1,500 CFM—75’ (22.9 m)

o For general reference only;

for longer duct runs, increase
duct size and contact a
qualified and trained installer.

o Straight runs and gradual

turns are best; for example,
each 90° elbow is equivalent
to 5’ – 10’ (1.52 – 3.05 cm) of
straight run.

• 7” (17.8 cm) round duct for

300 – 600 CFM; 10” for 900 –
1500 CFM
o Never use flexible duct; it

creates back pressure/air
turbulence and greatly
reduces performance.

GAS
Not applicable

ELECTRICAL
• Hardwire direct with two-wire

ground

• 120 VAC/60 Hz
• Max. amp usage (rating

includes recommended
ventilator kit rating)—see
Dimensions & Specifications
table

PLUMBING
Not applicable

DTWS Slim Traditional

Wall Hood

DTWN Tall

Traditional Ledgeless

Wall Hood

P L A N N I N G A N D D E S I G N G U I D E

V I K I N G R A N G E . C O M

1 - 8 8 8 - V I K I N G 1

VENTILATION

Designer Built-In Wall Hoods

Installation Requirements

* A 1,200 CFM interior- or exterior-power ventilator should be used when installed over range/rangetop with gas char-grill.
** It is recommended that the 1,500 CFM ventilator be used with longer duct runs.
Note: Maximum amp rating for hoods includes recommended ventilator kit rating. All products must be hard wired with two-wire ground. An interior- or
exterior-power ventilator kit must be purchased for installation with all 18”H. hoods.

Model

Ventilator Kits

Duct Size

Max. Amps

Interior

Exterior

Interior

Exterior

Interior

Exterior

DTWS3049

DIV300/440

DEV900/DIL900

7” (17.8 cm)

10” (25.4 cm)

1.7/3.2

6.6

DTWS3649

DIV300/440

DEV900/1200/DIL900/1200

7” (17.8 cm)

10” (25.4 cm)

1.7/3.2

6.6

DTWS4249

DIV440

DEV900/1200/DIL900/1200

7” (17.8 cm)

10” (25.4 cm)

3.2

6.6

DTWS4849

DIV880

DEV1200/1500**/DIL1200

10” (25.4 cm)

10” (25.4 cm)

5.6

4.3/5.1

DTWN3048

VIV300/600/1200* VEV900/1200*/DIL900/1200

7” (17.8 cm)

10” (25.4 cm)

2.4/4.6/6.6

6.6/3.9

DTWN3648

VIV300/600/1200* VEV900/1200*/DIL900/1200

7” (17.8 cm)

10” (25.4 cm)

2.4/4.6/6.6

6.6/3.9

DTWN4248

VIV600/1200*

VEV900/1200*/DIL900/1200

7” (17.8 cm)

10” (25.4 cm)

4.6/6.6

6.6/3.9

DTWN4848

VIV1200*

VEV1200/1500**/DIL1200

10” (25.4 cm)

10” (25.4 cm)

7.0

4.3/5.1

Note: All CFMs are based on tests with 0.1 static pressure. Without applying static pressure (some brands do not), CFM could be greatly
overstated.

UTILITY REQUIREMENTS

R E V I S E D 5 / 2 / 1 1

© 2 0 1 1 V R C — INFORMATION SUBJECT TO CHANGE