beautypg.com

Installation, Location of appliance, Ventilation – Tricity Bendix SG 205WL User Manual

Page 20: If it is installed in a room of volume less 5m, An air vent of effective area of 110cm, And 10m, An air vent of effective area 50cm, Is required, while if the volume exceeds 11m, And 11m

background image

20

INSTALLATION

Location of appliance

The appliance must not be installed in a bed-sitting
room of volume less than 20m

3

or in a bathroom or

shower room. It is essential that the appliance is
positioned as in the enclosed figure i.e. shelves, wall
cabinets and cooker hoods must be fitted a minimum
of 690mm directly above the hob and 400mm above
the hob when fitted in line with the outside of the
appliance. If the units are intended to be fitted
adjacent to the appliance but less than 400mm above
the hob, then a minimum space of 100mm must be
maintained between the sides of the unit and the
appliance (see fig).
If fitted next to or between two base units a
minimum space of 1mm must be left between each
unit and the sides of the appliance. The levelling
feet fitted to the appliance will achieve a nominal
height to hob of 900mm+10mm.
The appliance must be installed in accordance with
EN 1116-1995, regarding the depth of the superior
furniture.

L.P.G. cookers or ovens MUST NOT be

installed below ground level, i.e. in a basement,
or aboard any boat, yacht or other vessel.

The cooking appliance must be fitted with a

stability chain firmly secured to the wall (see
fig).

Ventilation

The room containing the cooker should have an air
supply in accordance with B.S. 5440: Part 2: Current
Editions.
The following requirements for ventilation must be
met.

The cooker should not be installed in a bed sitting
room with a volume of less than 20m

3

, if it is installed

in a room of volume less 5m

3

an air vent of effective

area of 110cm

2

is required; if it is installed in a room

of volume between 5m

3

and 10m

3

, an air vent of

effective area 50cm

2

is required, while if the volume

exceeds 11m

3

no air vent is required. However, if the

room has a door, which opens directly to the outside,
no air vent is required even when the volume is
between 5m

3

and 11m

3

.

If there are other fuels burning appliances in the
same room, B.S. 5440: Part. 2: Current Editions
should be consulted to determine the requisite air
vent requirements.

690

400

min 600

max 400

min 570

6

90

less than

400

100

C

21

3

45678

G

C

21

3

45678

G




Stability

chain

Stability

hook

Chain to be as

short as

practicable

Firmly fix

chain to rear

of cooker