4 service led display – MITSUBISHI ELECTRIC GB-50A User Manual
Page 8
7
2) Setting of the service switch
The switches must be OFF for normal use. The switch setting change works when the power is turned on
next time.
3-4 Service LED display
This unit comes with an LED that displays operation status.
Table 3-4 List of services LED
LED No.
Items
Contents
Power supply
LED
Powering status
ON
: Power is supplied
/ OFF: Power is cut off
LAN
LAN LINK
ON
: During LINK
/ OFF: No LINK
LAN
LAN ACT
Flicker: During communication
/ OFF: No communication
LED1
Start-up
ON : Start-up not completed
/ OFF : Start-up completed
LED2
Operation ON/OFF
ON
: 1 or more units are ON
/ OFF: All OFF
LED3
Error
Flicker: Error occurred on 1 or more units / OFF: Normal state
LED4 (not
defined)
-
LED5 (not
defined)
-
LED6 M-NET
communication
(transmission)
Flicker : During communication
/ OFF: No communication
1 2
Contents
Remarks
OFF OFF
Start up with the normal
mode
*This setting is for normal use.
ON
OFF -
Setting is prohibited.
OFF
ON
-
Setting is prohibited.
ON ON
Start up with the update
mode
*The software can be updated with the
normal mode. If the update fails, or the
software does not work properly use
this setting to update the software
again.
*SW1-3 and SW1-4 are always OFF.
Notes
●
When 15 or fewer GB-50A units are used in the designated network for air-conditioning, it is recommended that
the IP address be set using SW2 on the unit.
●
If the set IP address of GB-50A is forgotten, check the IP address that is registered on the monitoring PC (WEB
or TG-2000A). GB-50A can be started by changing the setting of SW2 on GB-50A and using an arbitrary fixed
IP address as a temporary IP address. It is recommended to paste a sticker with the IP address on the unit, so
that the IP address of GB-50A is available at all times. Once GB-50A is started up with a temporary IP address,
a new IP address can be assigned to it on the Initial Setting Web.
LED1-6
Power supply
LED
LAN
POWER LAN LINK/ACT 1 2 3 4 5 6
SW 1
1 2 3 4
Not to be used
ON
OFF