beautypg.com

3 setting functions – MITSUBISHI ELECTRIC GB-50A User Manual

Page 7

background image

6

3-3 Setting Functions

Make initial settings with either the Initial Setting Web or Initial Setting Tool.

Table 3-3 List of initial-setting functions

Item

This Unit

Initial Setting Tool

Initial Setting

Web

Remarks

M-NET address
setting

The default value is 0.

IP address setting

(simple setting)

The settings of the simple
setting have the priority
over other settings.

Function selection

Presence/absence of
K transmission converter
connection, local operation
prohibition setting, and external
input mode

Group registration

Registration of
interlocked
operation with the
Lossnay unit


Switch for start-up
mode


Other settings

Available functions vary
depending on the tools.

1) How to set the IP address with dipswitches

IP addresses between 192.168.1.1 and15 can be set using the 4-pin dip switch on SW2.
Set this switch before turning the power on.









Note

● When setting IP addresses with the Initial Setting Web or the Initial Setting Tool, set all four

dipswitches on SW2 to OFF.

1

2

3

4

Contents (IP address)

OFF OFF OFF OFF

Address that is set with Initial Setting Web or
Initial Setting Tool.
(Initial IP address setting is 192.168.1.1)

OFF OFF OFF ON Starts from 192.168.1.1
OFF OFF ON OFF Starts from 192.168.1.2
OFF OFF ON

ON Starts from 192.168.1.3

OFF ON OFF OFF Starts from 192.168.1.4
OFF ON OFF ON Starts from 192.168.1.5
OFF ON

ON OFF Starts from 192.168.1.6

OFF ON

ON

ON Starts from 192.168.1.7

ON OFF OFF OFF Starts from 192.168.1.8
ON OFF OFF ON Starts from 192.168.1.9
ON OFF ON OFF Starts from 192.168.1.10
ON OFF ON

ON Starts from 192.168.1.11

ON ON OFF OFF Starts from 192.168.1.12
ON ON OFF ON Starts from 192.168.1.13
ON ON

ON OFF Starts from 192.168.1.14

ON ON

ON

ON Starts from 192.168.1.15

(Inside the cover)

SW 2

1 2 3 4

ON
OFF