3-3 Setting Functions
Make initial settings with either the Initial Setting Web or Initial Setting Tool.
Table 3-3 List of initial-setting functions
Item
This Unit
Initial Setting Tool
Initial Setting
Web
Remarks
M-NET address
setting
√
√
The default value is 0.
IP address setting
√
(simple setting)
√
√
The settings of the simple
setting have the priority
over other settings.
Function selection
√
√
Presence/absence of
K transmission converter
connection, local operation
prohibition setting, and external
input mode
Group registration
√
√
Registration of
interlocked
operation with the
Lossnay unit
√
√
Switch for start-up
mode
√
Other settings
√
√
Available functions vary
depending on the tools.
1) How to set the IP address with dipswitches
IP addresses between 192.168.1.1 and15 can be set using the 4-pin dip switch on SW2.
Set this switch before turning the power on.
Note
● When setting IP addresses with the Initial Setting Web or the Initial Setting Tool, set all four
dipswitches on SW2 to OFF.
1
2
3
4
Contents (IP address)
OFF OFF OFF OFF
Address that is set with Initial Setting Web or
Initial Setting Tool.
(Initial IP address setting is 192.168.1.1)
OFF OFF OFF ON Starts from 192.168.1.1
OFF OFF ON OFF Starts from 192.168.1.2
OFF OFF ON
ON Starts from 192.168.1.3
OFF ON OFF OFF Starts from 192.168.1.4
OFF ON OFF ON Starts from 192.168.1.5
OFF ON
ON OFF Starts from 192.168.1.6
OFF ON
ON
ON Starts from 192.168.1.7
ON OFF OFF OFF Starts from 192.168.1.8
ON OFF OFF ON Starts from 192.168.1.9
ON OFF ON OFF Starts from 192.168.1.10
ON OFF ON
ON Starts from 192.168.1.11
ON ON OFF OFF Starts from 192.168.1.12
ON ON OFF ON Starts from 192.168.1.13
ON ON
ON OFF Starts from 192.168.1.14
ON ON
ON
ON Starts from 192.168.1.15
(Inside the cover)
SW 2
1 2 3 4
ON
OFF