3 function, 1. specification – MITSUBISHI ELECTRIC GB-50A User Manual

Page 5

background image

4


3-1. Specification

Table 3-1 Specification list

Item Specification

Interface

M-NET : DC30V/24V;0.13/0.15A
LAN : Ethernet 10Base-T
Input/output :DC12V or 24V (External power supply)
Temperature

Operating range 0 to 40

ºC / 32 to 104ºF

Storage range -20 to 60

ºC / -4 to 140ºF

Environmental condition

Humidity

30~90%RH (No condensation)

Dimensions 130(H)

250(W) ✕38 (D) mm/5

1

/

8

(H) ✕9

7

/

8

(W) ✕ 1

1

/

2

(D)in

Weight 1.1kg/ 2

1

/

2

lb

Installation Environment

In the control panel box (indoor)
*This unit is installed and used in a business office or equivalent
environment.








Number of control unit

Indoor unit or independent OA processing unit or LOSSNAY

: 50 units maximum (50 groups maximum)

Number of units (indoor or independent OA processing unit or LOSSNAY) in

one group
: 1-16 units

*Note Indoor unit, independent OA processing unit and LOSSNAY

can not register to the same group.

Number of remote controllers in one group

: 1-2

Number of system controllers in one group

: 0-4 (including the number of remote controller in one group)
: 0-3 for groups which have one remote controller.

Number of indoor units interlocked with one OA processing unit or
LOSSNAY

: 0-16 (some types of OA processing unit can only be operated
when interlocked to a maximum of 9 units)

Notes

● Refer to the WEB Browser Operation Manual for the operation of GB-50A.

● There are two ways to make the initial settings via LAN: one is to use the initial setting web and the

other is to use the initial setting tool. Either can be used to make the settings, although initial setting
web has more functions than the initial setting tool.

3 Function