CONDUCTORS AND CIRCUITS
INSTALLATION / OPERATION INSTRUCTIONS
Wire Gauge for 2% Voltage Drop in Supply Circuits
115 Volt
Distance In Feet To Center of Load
Amps 20 30 40 50 60 70 80 90 100 120 140 160
2
14 14 14 14 14 14 14 14 14 14 14 14
3
14 14 14 14 14 14 14 14 14 14 14 12
4
14 14 14 14 14 14 14 14 14 12 12 12
5
14 14 14 14 14 14 14 12 12 12 10 10
6
14 14 14 14 14 14 12 12 12 10 10 10
7
14 14 14 14 14 12 12 12 10 10 10 8
8
14 14 14 14 12 12 12 10 10 10 8 8
9
14 14 14 12 12 12 10 10 10 8 8 8
10
14 14 14 12 12 10 10 10 10 8 8 8
12
14 14 12 12 10 10 10 8 8 8 8 6
14
14 14 12 10 10 10 8 8 8 6 6 6
16
14 12 12 10 10 8 8 8 8 6 6 6
18
14 12 10 10 8 8 8 8 8 8 8 5
20
14 12 10 10 8 8 8 6 6 6 5 5
25
12 10 10 8
8
6
6
6
6
5
4
4
30
12 10 8 8 6 6 6 6 5 4 4 3
35
10 10 8 6 6 6 5 5 4 4 3 2
40
10 8 8 6 6 5 5 4 4 3 2 2
45
10 8 6 6 6 5 4 4 3 3 2 1
50
10 8 6 6 5 4 4 3 3 2 1 1
Wire Gauge for 2% Voltage Drop in Supply Circuits
230 Volts
Distance In Feet To Center of Load
Amps 20 30 40 50 60 70 80 90 100 120 140 160
5
14 14 14 14 14 14 14 14 14 14 14 14
6
14 14 14 14 14 14 14 14 14 14 14 12
7
14 14 14 14 14 14 14 14 14 14 12 12
8
14 14 14 14 14 14 14 14 14 12 12 12
9
14 14 14 14 14 14 14 14 12 12 12 10
10
14 14 14 14 14 14 14 12 12 12 10 10
12
14 14 14 14 14 14 12 12 12 10 10 10
14
14 14 14 14 14 12 12 12 10 10 10 8
16
14 14 14 14 12 12 12 10 10 10 8 8
18
14 14 14 12 12 12 10 10 10 8 8 8
20
14 14 14 12 10 10 10 10 10 8 8 8
25
14 14 12 12 10 10 10 10 8 8 6 6
30
14 12 12 10 10 10 8 8 8 6 6 6
35
14 12 10 10 10 8 8 8 8 6 6 5
40
14 12 10 10 8 8 8 6 6 6 5 5
50
12 10 10 8
6
6
6
6
6
5
4
4
60
12 10 8 6 6 6 6 6 5 4 4 3
70
10 10 8 6 6 6 5 5 4 4 2 2
80
10 8 8 6 6 5 5 4 4 3 2 2
90
10 8 6 6 5 5 4 4 3 3 1 1
100
10 8 6 6 5 4 4 3 3 2 1 1