6 ton) performance data – Trane PKGP-PRC003-EN User Manual

Page 32

background image

32

PKGP-PRC003-EN

(6 Ton)

Performance
Data

Table PD-32 — 6 Ton Heating Capacities (Net)

WSC72A

At 2400 CFM Downflow Configuration

Outdoor

Integrated Heating Capacity (Btuh/1000)

Total Power in Kilowatts at

Temp.

at Indicated Indoor Dry Bulb Temp.

1

Indicated Indoor Dry Bulb Temp.

F.

60

70

75

80

60

70

75

80

--8

23.9

23.4

23.2

23.0

4.40

4.75

4.95

5.17

-3

26.4

26.0

25.8

25.6

4.45

4.81

5.01

5.24

2

29.3

28.8

28.6

28.4

4.52

4.88

5.09

5.31

7

32.3

31.8

31.6

31.4

4.59

4.95

5.17

5.40

12

35.6

35.1

34.8

34.5

4.66

5.04

5.25

5.49

17

39.1

38.5

38.2

37.9

4.74

5.12

5.34

5.58

22

42.8

42.1

41.8

41.4

4.83

5.22

5.44

5.68

27

46.5

45.7

45.5

45.1

4.93

5.32

5.54

5.79

32

50.5

49.7

49.2

48.8

5.02

5.43

5.66

5.91

37

54.7

53.7

53.2

52.7

5.13

5.54

5.77

6.03

42

59.0

57.8

57.3

56.7

5.23

5.65

5.89

6.15

47

70.0

68.6

67.9

67.2

5.56

6.01

6.27

6.55

52

75.1

73.5

72.7

72.0

5.69

6.15

6.41

6.70

57

80.3

78.5

77.6

76.8

5.82

6.29

6.55

6.84

62

85.6

83.6

82.6

81.7

5.96

6.43

6.70

7.00

67

91.0

88.8

87.7

86.6

6.10

6.58

6.86

7.15

72

96.8

94.3

93.1

91.8

6.26

6.75

7.03

7.33

For other airflow conditions, see heating capacity correction factor (Table PD-39).
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this
condition and add fan heat at new condition.
Note:
1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70%

OD relative humidity and demand defrost cycle.

Table PD-33— 6 Ton Heating Capacities (Net)

WSC072A

At 2400 CFM Horizontal Configuration

Outdoor

Integrated Heating Capacity (Btuh/1000)

Total Power in Kilowatts at

Temp.

at Indicated Indoor Dry Bulb Temp.

1

Indicated Indoor Dry Bulb Temp.

F.

60

70

75

80

60

70

75

80

-8

24.2

23.7

23.5

23.3

4.48

4.83

5.03

5.25

-3

26.7

26.2

26.0

25.8

4.54

4.89

5.09

5.32

2

29.5

29.1

28.8

28.6

4.60

4.96

5.17

5.39

7

32.6

32.1

31.9

31.6

4.67

5.03

5.25

5.47

12

35.9

35.3

35.1

34.8

4.74

5.12

5.33

5.56

17

39.4

38.8

38.5

38.2

4.82

5.20

5.42

5.66

22

43.1

42.4

42.0

41.7

4.91

5.30

5.52

5.76

27

46.8

46.0

45.8

45.4

5.01

5.40

5.62

5.87

32

50.8

49.9

49.5

49.1

5.11

5.51

5.74

5.99

37

55.0

54.0

53.5

53.0

5.21

5.62

5.85

6.11

42

59.2

58.1

57.5

57.0

5.31

5.73

5.97

6.23

47

70.3

68.9

68.2

67.5

5.64

6.09

6.35

6.63

52

75.4

73.8

73.0

72.2

5.77

6.23

6.49

6.77

57

80.6

78.8

77.9

77.1

5.90

6.36

6.63

6.92

62

85.9

83.9

82.9

81.9

6.04

6.51

6.78

7.07

67

91.3

89.0

88.0

86.9

6.18

6.66

6.93

7.23

72

97.1

94.5

93.3

92.1

6.34

6.83

7.11

7.40

For other airflow conditions, see heating capacity correction factor (Table PD-39).
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this
condition and add fan heat at new condition.
Note:
1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70%

OD relative humidity and demand defrost cycle.