beautypg.com

General data (7½, 10 ton) – Trane PKGP-PRC003-EN User Manual

Page 16

background image

16

PKGP-PRC003-EN

General
Data

(7½, 10 Ton)

Table GD-3 — General Data

7½ Ton Convertible Units

10 Ton Convertible Units

WSC090A3, A4, AW

WSC120A3, A4, AW

Cooling Performance

1

Gross Cooling Capacity

93,000

121,000

EER

2

10.1

10.1

Nominal CFM / ARI Rated CFM

3,000/2,625

4,000/3,200

ARI Net Cooling Capacity

88,000

113,000

Integrated Part Load Value

10.7

System Power (KW)

8.71

11.19

Heating Performance

1

High Temp. Btuh Rating

88,000

108,000

System Power KW/COP

8.06/ 3.2

9.59/3.3

Low Temp. Btuh Rating

50,000

59,000

System Power KW/COP

6.66/2.2

7.86/2.2

HSPF (Btu/Watts-hr)

Compressor

No./Type

1/Scroll

2/Scrolls

Outdoor Sound Rating (dB)

3

90

88

Outdoor Coil — Type

Lanced

Lanced

Tube Size (in.) OD

.3125

.3125

Face Area (sq ft)

17.00

19.83

Rows/FPI

3/17

3/17

Refrigerant Control

Expansion Valve

Expansion Valve

Indoor Coil — Type

Lanced

Lanced

Tube Size (in.)

.3125

.3125

Face Area (sq ft)

9.89

12.36

Rows/FPI

4/16

4/16

Refrigerant Control

Short Orifice

Short Orifice

Drain Connection No./Size (in.)

1/¾ NPT

1/¾ NPT

Outdoor Fan — Type

Propeller

Propeller

No. Used/Diameter (in.)

1/26

1/26

Drive Type/No. Speeds

Direct/1

Direct/1

CFM

6,400

6,700

No. Motors/HP

1/.70

1/.75

Motor RPM

1,075

1,075

Belt Drive Indoor Fan — Type

FC Centrifugal

FC Centrifugal

No. Used

1

1

Diameter x Width (in.)

12 x 12

15 x 15

Drive Type/No. Speeds

Belt/Variable Speed

Belt/Variable Speed

No. Motors

1

1

Motor HP (Standard/Oversized)

1.00/3.00

2.00/ 5.00

Motor RPM (Standard/Oversized)

1,750/1,750

1,750/3,450

Motor Frame Size (Standard/Oversized)

56/56

56/56

Filters — Type Furnished

5

Throwaway

Throwaway

(No.) Size Recommended (in.)

(4) 16 x 25 x 2

(4) 20 x 25 x 2

Refrigerant Charge (Lbs of R-22)

4

12.2

7.9 Circuit #1/7.9 Circuit #2

Notes:
1. Cooling Performance and Heating Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb . Gross capacity does not include the effect of fan motor heat. ARI capacity is

net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification
program, which is based on ARI Standard 210/240.

2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-25.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Optional 2 inch pleated filters are also available.