beautypg.com

Performance data – Trane TSC060-120 User Manual

Page 25

background image

25

RT-PRC016-EN

Performance
Data

Table PD-12 — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.50 Nom kW Standard Motor & Low Static Drive

1.50 Nom kW Standard Motor & Drive

4620

-

-

-

-

-

-

613

0.45

655

0.54

695

0.62

733

0.71

769

0.81

802

0.90

833

1.00

5200

-

-

-

-

611

0.48

650

0.55

688

0.64

725

0.73

761

0.83

796

0.93

828

1.03

861

1.13

5780

-

-

612

0.51

651

0.59

689

0.68

724

0.76

759

0.86

792

0.96

825

1.07

856

1.18

887

1.28

6350

622

0.56

659

0.64

693

0.72

729

0.82

764

0.92

795

1.01

826

1.11

857

1.22

887

1.34

916

1.46

6930

671

0.71

706

0.80

738

0.89

770

0.98

804

1.09

834

1.19

864

1.30

892

1.40

920

1.52

948

1.64

1.50 Nom kW Standard
Motor & Hi Static Drive

← ← ← ← ←

External Static Pressure (Pascals)

275

300

325

350

375

400

425

450

475

500

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.50 Nom kW Std Mtr & Drive

1.50 Nom kW Std Mtr & Hi Static Dr

4620

863

1.11

892

1.21

920

1.33

946

1.44

973

1.55

999

1.67

1025

1.79

1050

1.90

1073

2.02

1098

2.14

5200

891

1.24

919

1.35

946

1.46

973

1.58

999

1.71

1024

1.83

1048

1.96

1072

2.09

1096

2.22

1119

2.34

5780

917

1.40

946

1.51

974

1.63

1001

1.75

1026

1.88

1051

2.01

1074

2.14

1099

2.27

1121

2.41

1143

2.55

6350

945

1.58

974

1.70

1001

1.82

1028

1.95

1054

2.08

1079

2.20

1103

2.34

1126

2.48

1148

2.62

1170

2.76

6930

976

1.78

1002

1.91

1029

2.04

1055

2.17

1081

2.30

1105

2.43

1130

2.58

1154

2.72

1176

2.85

1199

3.01

2.24 Nom kW Over-Sized Motor & High Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

Table PD-12a — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (IP)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2 HP Standard Motor & Low Static Drive

2 HP Standard Motor & Drive

2720

-

-

-

-

-

-

613

0.60

655

0.72

695

0.84

733

0.95

769

1.08

802

1.21

833

1.34

3060

-

-

-

-

611

0.64

650

0.74

688

0.85

725

0.98

761

1.11

796

1.25

828

1.38

861

1.52

3400

-

-

612

0.68

651

0.79

689

0.91

724

1.02

759

1.15

792

1.29

825

1.43

856

1.58

887

1.72

3740

622

0.76

659

0.86

693

0.97

729

1.10

764

1.23

795

1.35

826

1.49

857

1.64

887

1.79

916

1.96

4080

671

0.96

706

1.08

738

1.19

770

1.32

804

1.46

834

1.60

864

1.74

892

1.88

920

2.04

948

2.20

2 HP Standard Motor &
Hi Static Drive

← ← ← ← ←

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2 HP Standard Mtr & Drive

2 HP Std Motor & Hi Static Drive

2720

863

1.48

892

1.63

920

1.78

946

1.93

973

2.08

999

2.24

1025

2.39

1050

2.55

1073

2.71

1098

2.88

3060

891

1.66

919

1.81

946

1.96

973

2.12

999

2.29

1024

2.46

1048

2.63

1072

2.80

1096

2.98

1119

3.14

3400

917

1.87

946

2.03

974

2.18

1001

2.34

1026

2.52

1051

2.69

1074

2.86

1099

3.05

1121

3.23

1143

3.41

3740

945

2.11

974

2.28

1001

2.44

1028

2.61

1054

2.78

1079

2.96

1103

3.14

1126

3.32

1148

3.51

1170

3.71

4080

976

2.38

1002

2.56

1029

2.73

1055

2.91

1081

3.09

1105

3.26

1130

3.45

1154

3.65

1176

3.83

1199

4.03

3 HP Over-Sized Motor & Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.