Performance
Data

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1/2 HP Standard Motor & Drive

1-1/2 HP Standard Motor & Hi Static Drive

1600

1206

1.12

1241

1.20

1275

1.28

1306

1.37

1338

1.46

1800

1256

1.32

1291

1.41

1326

1.50

1359

1.60

1390

1.69

2000

1309

1.56

1343

1.66

1376

1.76

-

-

-

-

2200

-

-

-

-

-

-

-

-

-

-

2400

-

-

-

-

-

-

-

-

-

-

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

External Static Pressure (Pascals)

275

300

325

350

375

CFM

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 Nom kW Standard Motor & Drive

2720

1206

0.83

1241

0.89

1275

0.96

1306

1.02

1338

1.09

3060

1256

0.99

1291

1.05

1326

1.12

1359

1.19

1390

1.26

3400

1309

1.16

1343

1.24

1376

1.31

-

-

-

-

3740

-

-

-

-

-

-

-

-

-

-

4080

-

-

-

-

-

-

-

-

-

-

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132

1.12 Nom kW Standard Motor &
Hi Static Drive

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-7 - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 Nom kW Std Motor & Low Static Drive

1.12 Nom kW Standard Motor & Drive

2720

707

0.26

774

0.31

837

0.37

898

0.43

953

0.48

1001

0.54

1045

0.59

1087

0.65

1129

0.71

1168

0.77

3060

778

0.36

840

0.41

897

0.48

953

0.54

1008

0.60

1058

0.67

1102

0.73

1143

0.79

1181

0.85

1219

0.92

3400

850

0.48

908

0.54

961

0.60

1012

0.67

1062

0.74

1111

0.81

1157

0.88

1198

0.95

1237

1.02

1274

1.09

3740

923

0.63

978

0.69

1028

0.76

1075

0.83

1120

0.91

1166

0.99

1211

1.06

1254

1.14

1294

1.22

1330

1.29

4080

997

0.80

1049

0.87

1096

0.94

1140

1.02

1183

1.10

1223

1.18

1266

1.27

-

-

-

-

-

-

1.12 Nom kW Standard Motor & Hi Static Drive

← ← ← ← ←

Table PD-7a - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (IP)

External Static Pressure (Inches of Water)

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-1/2 HP Standard Motor &

Low Static Drive

1-1/2 HP Standard Motor & Drive

1600

707

0.35

774

0.42

837

0.50

898

0.57

953

0.65

1001

0.72

1045

0.80

1087

0.87

1129

0.95

1168

1.03

1800

778

0.48

840

0.56

897

0.64

953

0.72

1008

0.81

1058

0.89

1102

0.98

1143

1.06

1181

1.15

1219

1.23

2000

850

0.65

908

0.73

961

0.81

1012

0.90

1062

1.00

1111

1.09

1157

1.19

1198

1.28

1237

1.37

1274

1.47

2200

923

0.84

978

0.93

1028

1.02

1075

1.12

1120

1.22

1166

1.32

1211

1.43

1254

1.53

1294

1.63

1330

1.74

2400

997

1.07

1049

1.17

1096

1.27

1140

1.37

1183

1.48

1223

1.59

1266

1.70

-

-

-

-

-

-

1-1/2 HP Standard Motor & Hi Static Drive

← ← ← ← ←