Programming installation – Trane IntelliPak SCWG 020 User Manual

Page 69

background image

SCXG-SVX01B-EN

69

Table I-P-1. Zone Sensor BAYSENS019 Option Menu Settings.

Option #

Description

Value

Factory Setting

1

Morning Warmup

0 = Disabled

0

1 = Enabled

2

Economizer minimum

0 = Disabled

1

Position override

1 = Enabled

3

Temperature Scale

0 = Fahrenheit

0

1 = Enabled

4

Supply Air Tempering

0 = Disabled

0

1 = Enabled

5

Time Clock

0 = 12 hours

0

1 = 24 hours

6

Smart Fan

0 = Disabled

1

1 = Enabled

7

Intelligent Temperature Recovery

0 = Disabled

0

1 = Enabled

8

Programmable Days/Week

0 = 7 days (M,T,W,T,F,S,S)

0

1 = 3 days (M-F, S, S)

2 = 2 days (M-F, S,S)

9

Programmable Periods/Day

2,3,4

4

10

Programmable Fan Operation

0 = Disallowed

0

1 = Allowed

11

Remote Sensor Installed

0 = No

0

1 = Yes

12

Check Filter Interval

0 = Disabled

350

3000 to 50 in 50 hour

increments

13

Display Zone Temperature

0 = No

1

1 = Yes

14

Keypad Lockout Enabled

0 = Disabled

1

1 = Enabled

15

Initial Time Setting in Temporary

1,2,3,4,5

3

Override Mode (hrs.)

16

Buzzer Options

0 = Key Press only

1

1 = Key Press & Check filter
2 = Key Press, Check Filter,

and System Failures

17

Zone Temperature Calibration

Displays current temp.

0 offset

with any offsets

18

Baud Rate

0 = 1024 baud

1

1 = 1200 baud

19

CV or HP Operation

0 = CV

0

1 = HP

20

Default Cooling setpoint

45 to 98 F

74 F

21

Default Heating setpoint

43 to 96 F

68 F

22

Minimum Cooling Setpoint

45 to 98 F

45 F

23

Maximum Heating Setpoint

43 to 96 F

96 F

Programming

Installation

Figure I-P-8. Typical option menu screen.

Option Menu and Keypad Operation
The operation menu sets all
programmable options built into your
ZSM. All options are retained in
permanent EEPROM memory.

To access the option menu display,
simultaneously depress and hold the
mode button and program button for four
seconds. See Figure I-P-8.

The example in Figure I-P-8 shows option
15 displayed and indicates the initial timer
setting in the temporary override run
mode. The option value shown is in
hours, and value selected is five hours.

When the option menu displays, the only
active buttons are the

­ or ¯ arrow and

the “minus” and “plus” button. The

­ or

¯ arrow increment through the available
options by number (1-24), and the
“minus” and “plus” button toggles
through the various option values
associated with each option number. See
Table I-P-1.

Note: On both programmable zone sensor
options, changing either option 9 or 10 will
erase the current program. To avoid
reprogramming, set options 9 and 10
before programming.