Table GD-1. Force–Flo Cabinet Heater General Data
Unit Size
02
03
04
06
08
10
12
Coil Data
Face Area — Ft
2
(cm
2
)
0.8 (743)
0.8 (743)
1.1 (1020)
1.6 (1490)
2.1 (1950)
3.2 (2970)
3.2 (2970)
LxDxH — In. (cm)
2-Row
15x1.7x8
15x1.7x8
20x1.7x8
29.5x1.7x8
38x1.7x8
57x1.7x8
57x1.7x8
(38x4x20)
(38x4x20)
(51x4x20)
(75x4x20)
(97x4x20)
(145x4x20)
(145x4x20)
3-Row
15x2.6x8
15x2.6x8
20x2.6x8
29.5x2.6x8
38x2.6x8
57x2.6x8
57x2.6x8
(38x7x20)
(38x7x20)
(51x7x20)
(75x7x20)
(97x7x20)
(145x7x20)
(145x7x20)
4-Row
15x3.5x8
15x3.5x8
20x3.5x8
29.5x3.5x8
38x3.5x8
57x3.5x8
57x3.5x8
(38x9x20)
(38x9x20)
(51x9x20)
(75x9x20)
(97x9x20)
(145x9x20)
(145x9x20)
Volume — Gal. (Liters)
1-Row (Heat)
.06 (.23)
.06 (.23)
.08 (.30)
.11 (.42)
.14 (.53)
.21 (.79)
.21 (.79)
2-Row
.12 (.45)
.12 (.45)
.15 (.57)
.22 (.83)
.28 (1.06)
.42 (1.59)
.42 (1.59)
3-Row
.18 (.68)
.18 (.68)
.23 (.87)
.33 (1.25)
.42 (1.59)
.62 (2.35)
.62 (2.35)
4-Row
.24 (.91)
.24 (.91)
.30 (1.14)
.44 (1.67)
.56 (2.12)
.83 (3.14)
.83 (3.14)
Fins/Ft (cm)
2-Row
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
3-Row
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
4-Row
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
Fan/Motor Data
Fan Quantity
1
1
1
2
2
3
3
Size — Dia” x Width” (cm)
6.31x4
6.31x6.5
6.31x7.5
6.31x6.5
6.31x7.5
(1) 6.31x7.5
6.31x7.5
(16x10)
(16x17)
(16x19)
(16x17)
(16x19)
(16x19)
(16x19)
(2) 6.31x6.5
(16x6.5)
Motor Quantity
1
1
1
1
1
2
2
Filter Data
1” (cm) TA and Pl. Media
Quantity
1
1
1
1
1
1
1
Size — In. (cm)
8
7
/
8
x 19
1
/
8
8
7
/
8
x 19
1
/
8
8
7
/
8
x 24
1
/
8
8
7
/
8
x 33
5
/
8
8
7
/
8
x 42
1
/
8
8
7
/
8
x 61
1
/
8
8
7
/
8
x 61
1
/
8
(23x49)
(23x49)
(23x61)
(23x85)
(23x107)
(23x155)
(23x155)
1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity
1
1
1
1
1
1
1
Size — In. (cm)
5
1
/
2
x 19
1
/
8
5
1
/
2
x 19
1
/
8
5
1
/
2
x 24
1
/
8
5
1
/
2
x 33
5
/
8
5
1
/
2
x 42
1
/
8
5
1
/
2
x 61
1
/
8
5
1
/
2
x 61
1
/
8
(14 x 49)
(14 x 49)
(14 x 61)
(14 x 85)
(14 x 107)
(14 x 156)
(14 x 156)
Table GD-2. Cabinet Heater Air Flow
ESP
FD Motor
High Static Motor
Unit Size
Coil
0.05
0.1
0.2
0.3
0.4
2R144
240
330
300
280
250
02
3R144
230
330
300
270
240
4R144
200
300
270
250
220
2R144
320
410
390
350
320
03
3R144
310
400
360
330
290
4R144
280
370
340
300
270
2R144
390
450
410
380
340
04
3R144
370
550
510
470
430
4R144
340
510
480
440
400
2R144
610
760
700
650
590
06
3R144
610
890
830
770
710
4R144
560
820
760
710
660
2R144
800
1020
960
890
820
08
3R144
730
1000
930
870
800
4R144
680
940
870
810
750
2R144
980
1260
1180
1090
1010
10
3R144
1000
1400
1310
1210
1120
4R144
930
1300
1220
1130
1040
2R144
1110
1430
1330
1240
1140
12
3R144
1080
1520
1420
1330
1220
4R144
1000
1430
1340
1240
1150
Note: This is data is based on horizontal concealed model only, with duct inlet, duct outlet and no filter, dry coil, all voltages
except 208 V.