Table PAF-1. Pressure drop correction factor

Leaving

Water

Percent of Ethylene Glycol

Temperature

0

10

20

30

40

50

0

NA

NA

NA

NA

1.50

1.60

10

NA

NA

NA

1.38

1.46

1.55

20

NA

NA

1.26

1.34

1.42

1.51

30

NA

1.15

1.22

1.30

1.38

1.47

40

1.00

1.12

1.19

1.26

1.34

1.42

50

1.00

1.09

1.16

1.23

1.31

1.39

60

1.00

1.05

1.09

1.12

1.16

1.21

Table PAF-2. Pressure drop correction factor

Leaving

Water

Percent of Propylene Glycol

Temperature

0

10

20

30

40

50

0

NA

NA

NA

NA

1.63

1.90

10

NA

NA

NA

1.42

1.55

1.74

20

NA

NA

1.24

1.34

1.46

1.62

30

NA

1.11

1.19

1.28

1.39

1.53

40

1.00

1.07

1.15

1.23

1.33

1.45

50

1.00

1.04

1.11

1.19

1.28

1.39

60

1.00

1.00

1.03

1.08

1.13

1.20

Figure PAF-3. Ethylene glycol and propylene glycol solution freezing points