Part load performance performance data – Trane CGWF User Manual
Page 23
23
CG-PRC012-EN
Table PD-5. Part-load performance for CGWF 20-60 ton – 60 Hz in English units
Unit Size
100%
IPLV
Tons
19.9
20
kW
15.2
20.3
EER
15.5
Tons
24.5
25
kW
19.0
20.5
EER
15.4
Tons
29.2
30
kW
22.8
20.3
EER
15.3
Tons
39.4
40
kW
30.1
20.7
EER
15.6
Tons
48.6
50
kW
37.6
19.6
EER
15.4
Tons
59.4
60
kW
46.5
19.8
EER
15.2
Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. EER and IPLV values include compressor and control kW.
3. kW input is for compressors only.
Table PD-6. Part-load performance for CGWF 20-60 ton – 50 Hz in English units
Unit Size
100%
IPLV
Tons
16.7
20
kW
12.4
21.0
EER
16.1
Tons
20.6
25
kW
15.5
20.9
EER
16.0
Tons
24.5
30
kW
18.5
20.7
EER
15.9
Tons
33.0
40
kW
24.5
21.3
EER
16.2
Tons
40.8
50
kW
30.6
20.3
EER
16.0
Tons
50.1
60
kW
37.6
20.4
EER
16.0
Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. EER and IPLV values include compressor and control kW.
3. kW input is for compressors only.
Part Load
Performance
Performance
Data