Full load performance performance data – Trane CGWF User Manual
Page 22
CG-PRC012-EN
22
Table PD-9. 60 Hz CCAF performance data in Metric units
Evaporator
Entering Condenser Air Temperature (C)
Leaving Water
Unit
Condenser
30
35
40
45
Temperature (C)
Size
Size
kWo
kWi
COP
kWo
kWi
COP
kWo
kWi
COP
kWo
kWi
COP
20
CAUC-C20
69.4
19.8
3.5
66.2
21.7
3.0
62.5
23.8
2.6
58.7
26.2
2.2
20
CAUC-C25
70.7
18.9
3.7
67.3
20.7
3.2
63.8
22.9
2.8
60.3
25.1
2.4
25
CAUC-C25
86.2
25.3
3.4
82.1
27.8
2.9
77.8
30.5
2.5
73.1
33.5
2.2
25
CAUC-C30
87.8
23.8
3.7
84.0
26.2
3.2
79.7
28.8
2.8
75.2
31.7
2.4
6
30
CAUC-C30
103.0
29.6
3.5
98.2
32.4
3.0
93.1
35.6
2.6
87.9
39.1
2.2
30
CAUC-C40
104.7
27.4
3.8
100.3
30.1
3.3
95.3
33.1
2.9
90.2
36.4
2.5
40
CAUC-C40
138.4
39.5
3.5
131.9
43.3
3.0
124.8
47.6
2.6
117.5
52.4
2.2
40
CAUC-C50
140.0
38.1
3.7
133.6
41.9
3.2
126.8
46.0
2.7
119.5
50.7
2.3
50
CAUC-C50
170.2
51.0
3.3
162.3
56.0
2.9
153.8
61.5
2.5
144.8
67.5
2.1
50
CAUC-C60
173.5
47.8
3.6
165.7
52.5
3.1
157.6
57.9
2.7
149.0
63.7
2.3
60
CAUC-C60
203.5
59.2
3.4
194.1
65.2
3.0
184.2
71.6
2.6
173.6
78.7
2.2
60
CAUC-C80
206.0
54.5
3.8
197.0
59.9
3.3
187.6
66.1
2.8
177.5
72.7
2.4
20
CAUC-C20
73.5
20.2
3.6
70.0
22.1
3.1
66.2
24.3
2.7
62.3
26.7
2.3
20
CAUC-C25
74.8
19.2
3.9
71.5
21.1
3.4
67.7
23.3
2.9
63.9
25.5
2.5
25
CAUC-C25
91.3
25.8
3.5
86.8
28.3
3.1
82.4
31.0
2.6
77.6
34.1
2.3
25
CAUC-C30
93.3
24.3
3.8
89.1
26.6
3.3
84.6
29.3
2.9
79.9
32.1
2.5
8
30
CAUC-C30
109.1
30.2
3.6
104.0
33.0
3.1
98.9
36.2
2.7
93.2
39.8
2.3
30
CAUC-C40
111.1
27.8
4.0
106.3
30.5
3.5
101.4
33.6
3.0
96.1
36.9
2.6
40
CAUC-C40
146.1
39.5
3.7
139.3
44.0
3.1
132.2
48.5
2.7
124.6
53.2
2.3
40
CAUC-C50
148.0
38.6
3.8
141.3
42.4
3.3
134.3
46.7
2.9
126.9
51.4
2.5
50
CAUC-C50
179.9
52.0
3.4
171.5
56.9
3.0
162.8
62.5
2.6
153.3
68.7
2.2
50
CAUC-C60
183.7
48.5
3.8
175.6
53.4
3.3
167.0
58.7
2.8
158.0
64.6
2.4
60
CAUC-C60
215.1
60.4
3.5
205.4
66.3
3.1
195.1
72.8
2.7
184.3
80.0
2.3
60
CAUC-C80
217.9
55.3
3.9
208.6
61.0
3.4
198.6
67.0
3.0
188.4
73.8
2.5
20
CAUC-C20
77.4
20.6
3.7
73.8
22.6
3.3
70.0
24.7
2.8
65.9
27.1
2.4
20
CAUC-C25
78.9
19.6
4.0
75.4
21.5
3.5
71.9
23.6
3.0
67.8
25.9
2.6
25
CAUC-C25
96.4
26.2
3.7
92.0
28.8
3.2
87.2
31.6
2.7
82.4
34.6
2.4
25
CAUC-C30
98.7
24.6
4.0
94.2
27.0
3.5
89.7
29.7
3.0
84.7
32.5
2.6
10
30
CAUC-C30
115.2
30.7
3.7
110.1
33.7
3.3
104.6
36.9
2.8
98.9
40.4
2.4
30
CAUC-C40
117.5
28.3
4.1
112.7
31.0
3.6
107.3
34.0
3.1
101.8
37.4
2.7
40
CAUC-C40
154.0
40.9
3.7
147.0
44.9
3.3
139.6
49.2
2.8
131.7
54.1
2.4
40
CAUC-C50
156.0
39.3
3.9
149.3
43.1
3.4
142.0
47.4
3.0
134.0
52.1
2.6
50
CAUC-C50
189.7
52.9
3.6
181.1
57.9
3.1
171.8
63.5
2.7
162.3
69.8
2.3
50
CAUC-C60
193.9
49.3
3.9
185.6
54.1
3.4
176.6
59.6
3.0
167.1
65.4
2.5
60
CAUC-C60
227.2
61.6
3.7
216.9
67.6
3.2
206.4
74.1
2.8
195.0
81.4
2.4
60
CAUC-C80
230.4
56.1
4.1
220.8
61.6
3.6
210.2
67.9
3.1
199.4
74.7
2.7
Notes:
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kWi input is for compressors only.
4. COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5. Ratings are based on an evaporator temperature drop of 5.6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Rated in accordance with ARI Standard 550/590-98.
Full Load
Performance
Performance
Data