4-3. caution at servicing – Toshiba RAS-10YKV-E User Manual

Page 44

background image

– 44 –

Block distinction

Operation of diagnosis function

Check

code

Block

Check

code

Cause of operation

Air

conditioner

status

Remarks

Judgment and action

Short-circuit or
disconnection of the room
temperature sensor
(TA sensor).

Operation
continues.

Displayed when
error is detected.

1. Check the room temp. sensor.

2. When the room temp. sensor is

normal, check P.C. board.

Being out of place,
disconnection, short-
circuit, or migration of
heat exchanger sensor
(TC sensor)

Operation
continues.

Displayed when
error is detected.

1. Check heat exchanger sensor.

2. When heat exchanger sensor is

normal, check P.C. board.

Indoor P.C.
board etc.

Lock of indoor fan or
trouble on the indoor fan
circuit

All off

Displayed when
error is detected.

1. Check P.C. board.

2. When P.C. board is normal, check

the motor.

Not
displayed

Trouble on other indoor
P.C. boards

Operation
continues.

Displayed when
error is detected.

Replace P.C. board.

Return serial signal is not
sent to indoor side from
operation started.

(1) Defective wiring of

connecting cable

(2) Operation of

compressor thermo.
Gas shortage
Gas leak

Operation
continues.

Flashes when
trouble is detected
on Return serial
signal, and normal
status when signal
is reset.

1. When the outdoor unit never

operate:

(1) Check connecting cable, and

correct if defective wiring.

(2) Check 25A fuse of inverter P.C.

board.

(3) Check 3,15A of inverter P.C.

board.

2. To display [Other] block during

operation, check compressor
thermo. operation and supply gas
(check gas leak also).

3. Unit operates normally during check.

If Return serial signal does not stop
between indoor terminal board 2 and
3, replace inverter P.C. board.
If signal stops between indoor
terminal board 2 and 3, replace
indoor P.C. board.

Connecting
cable and
serial signal

Operation command
signal is not sent to
outdoor side.

Operation
continues

Flashes when
trouble is detected
on Operation
command signal,
and normal status
when signal is
reset.

If Return serial signal does not stop
between indoor terminal board 2 and 3,
replace inverter P.C. board.
If signal stops between indoor terminal
board 2 and 3, replace indoor P.C.
board.

10-4-3. Caution at Servicing

(1) After servicing, push the START/STOP button to return to the normal mode.

(2) After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power

supply again so that memory in the microcomputer returns the initial status. However, the check codes are
not deleted even if the power supply is turned off because they are stored in the fixed memory.