How to diagnose the trouble, 1. first confirmation – Toshiba RAS-10YKV-E User Manual

Page 40

background image

– 40 –

Discharging position
(Discharging period
10 seconds or more)

Plug of
soldering iron

Inverter cover

P. C. board
(Soldered surface)

MCC-808

10. HOW TO DIAGNOSE THE TROUBLE

The pulse modulating circuits are mounted to both
indoor and outdoor units. Therefore, diagnose
troubles according to the trouble diagnosis proce-
dure as described below. (Refer to the check points
in servicing written on the wiring diagrams attached
to the indoor/outdoor units.)

Table 10-1

No.

Troubleshooting Procedure

Page

1

First Confirmation

40

2

Primary Judgment

41

3

Judgment by Flashing LED of Indoor Unit

42

4

Self-Diagnosis by Service Check Remote

43

Controller

5

Judgment of Trouble by Every Symptom

46

6

How to Check Simply the Main Parts

53

NOTE :

A large-capacity electrolytic capacitor is used in the
outdoor unit controller (inverter). Therefore, if the
power supply is turned off, charge (charging voltage
DC280V) remains and discharging takes a lot of
time. After turning off the power source, if touching
the charging section before discharging, an electri-
cal shock may be caused. Discharge the electrolytic
capacitor completely by using soldering iron, etc.

< Discharging method >

(1) Remove the inverter cover (plating) by opening

four mounting claws.

(2) As shown below, connect the discharge resis-

tance (approx. 100

40W) or plug of the solder-

ing iron to voltage between + – terminals of the
C14 (“CAUTION HIGH VOLTAGE 320V” is
indicated.) electrolytic capacitor (500µF/400V)
on P.C. board, and then perform discharging.

Fig. 10-1

10-1. First Confirmation

10-1-1. Confirmation of Power Supply

Confirm that the power breaker operates (ON)
normally.

10-1-2. Confirmation of Power Voltage

Confirm that power voltage is AC 220–230–240 ±
10%. If power voltage is not in this range, the unit
may not operate normally.