Installation, Electrical installation – Thermador ME272 User Manual
Page 12

English 10
Installation
Electrical Installation
All model ovens on the front cover are dual rated, designed to be connected to
either 208/240V AC, 60 Hz, 4 wire, single-phase power supply.
The electrical supply should be a 4-wire single-phase AC. Install a suitable conduit
box (not furnished). An appropriately-sized, UL-listed conduit connector must be
used to correctly attach the conduit to the junction box.
Important: Local Codes may vary; installation, electrical connections and
grounding must comply with all applicable local codes.
If local codes permit grounding through the electrical supply neutral, connect both
the white neutral wire and the bare ground wire from the oven to the white neutral
electrical supply wire.
Model
Circuit Required
208V, 60 Hz
240V, 60 Hz
M271, M301
25 AMP
30 AMP
ME301, MEW301
ME271, PO301,
POD301, DE301,
DEC301
30 AMP
30 AMP
ME302, MED302,
ME272, MED272,
PO302, POD302,
PODC302, DE302,
MEM271, MEM301,
POM301, MEMC301,
MEMCW301,
MEMW271, MEMW301,
POMW301
40 or 50 Amp circuit. Refer to local electrical codes
for de-rating requirements.