beautypg.com

Performance adjustment factors – Trane RT-PRC007-EN User Manual

Page 18

background image

RT-PRC007-EN

18

Performance
Adjustment
Factors

Wet Bulb Temperature

Btu Per Lb.

40

15.23

41

15.70

42

16.17

43

16.66

44

17.15

45

17.65

46

18.16

47

18.68

48

19.21

49

19.75

50

20.30

51

20.86

52

21.44

53

22.02

54

22.62

55

23.22

56

23.84

57

24.48

58

25.12

59

25.78

60

26.46

61

27.15

62

27.85

63

28.57

64

29.31

65

30.06

66

30.83

67

31.62

68

32.42

69

33.25

70

34.09

71

34.95

72

35.83

73

36.74

74

37.66

75

38.61

Table PD-2 — Cooling Capacity Altitude Correction Factors

Altitude (Ft.)

Sea Level

1000

2000

3000

4000

5000

6000

7000

Cooling Capacity
Multiplier

1.00

0.99

0.99

0.98

0.97

0.96

0.95

0.94

KW Correction
Multiplier
(Compressors)

1.00

1.01

1.02

1.03

1.04

1.05

1.06

1.07

SHR Correction
Multiplier

1.00

.98

.95

.93

.91

.89

.87

.85

Maximum
Condenser
Ambient

115 F

114 F

113 F

112 F

111 F

110 F

109 F

108 F

Note:
SHR = Sensible Heat Ratio

Figure PD-1 — Air Density Ratios

Altitude/Temperature Correction

Air Density
Ratio (Density
at New
Air Density)
Condition/Std.

Rooftop Leaving Air Temperature (degrees F)

Table PD-3 — Gas Heating Capacity Altitude Correction Factors

Altitude (Ft.)

Sea Level

2001

2501

3501

4501

5501

6501

To 2000

To 2500

To 3500

To 4500

To 5500

To 6500

To 7500

Capacity
Multiplier

1.00

.92

.88

.84

.80

.76

.72

Note:
Correction factors are per AGA Std 221.30 — 1964, Part VI, 6.12. Local codes may supersede.

Table PD-1— Enthalpy of Saturated AIR