The rated temperature rise
represents a temperature rise for the motor's
rated current (full laod current).
This value is usually submitted by a motor
manufacturer as test data.
This relay requires setting of the motor's heating time constant and the cooling
time constant. These values are also supplied as the motor data.
When they are
not shown. request them from the motor manufacturer.
As a reference. the standard values of Toshiba motors are shown in Table 6.
Table 6 Heating Time Constant of Motor
(Toshiba Standard Values)
Motor kind
Time constant
(minute)
Totally
Other than totally Heating Cooling
Frame
enclosed
enclosed outer fan TR
I I
TD
outer fan
2 poles
4 pole
or more
355
30
400
355
45
4
450-630
400-630
60
560,
90
710
120