Drain piping work, Piping/heat insulating material, Flexible hose – Toshiba Carrier RAV-SP180UT-UL EN User Manual

Page 14: Caution

background image

Toshiba

– 13 –

4-way Air Discharge Cassette Type

Installation Manual

5

DRAIN PIPING WORK

CAUTION

Following the Installation Manual, perform the

drain piping work so that water is properly
drained, and apply a heat insulation so as not to
cause a dew droping.
Inappropriate piping work may result in water
leakage in the room and wet of furniture.

„

Piping/Heat insulating material

Require the following materials for piping and heat
insulating at site.

„

Flexible hose

Use the attached flexible hose to adjust center
discrepancy of the hard vinyl chloride pipe or to adjust
the angle.
• Do not use the flexible hose as stretched, or do not

deform it more extent than that in the following figure.

• Be sure to fix the soft end of the flexible hose with the

attached hose band.

• Use the flexible hose on a horizontal level.

REQUIREMENT

• Be sure to perform heat insulation of the drain pipes

of the indoor unit.

• Never forget to perform heat insulation of the connecting

part with the indoor unit.
An incomplete heat insulation causes dew droping.

• Set the drain pipe with downward slope (1/100 or

more), and do not make swelling or trap on the
piping. It may cause an abnormal sound.

• For length of the traversing drain pipe, restrict to

65’7” (20 m) or less.
In case of a long pipe, provide support brackets with
interval of 4’11” - 6’7” (1.5 - 2 m) in order to prevent
waving.

• Set the collective piping as shown in the below

figure.

• Be sure not to apply force to the connecting part of

the drain pipe.

• The hard vinyl-chloride pipe cannot be directly

connected to the drain pipe connecting port of the
indoor unit.
For connection with the drain pipe connecting port,
be sure to use/fix the attached flexible hose with the
hose band, otherwise a damage or water leak is
caused on the drain pipe connecting port.

Piping

Hard vinyl chloride pipe VP25

(Outer dia. : Ø1.3" (32 mm))

Heat insulator

Foam polyethylene :

Thickness 0.4" (10 mm) or more

max

45°

Riser (Trap)

90° Bend

max

45°

OK

NO GOOD

Support

bracket

1/100 or more

downward

Heat insulator

4’11” - 6’7” (1.5 - 2 m)

Arched

shape

Trap

NO

GOOD

VP25

As long as possible (3.9” (100 mm))

Downward slope

1/100 or more

VP30 or more

VP25

VP25

Drain pipe

connecting port

(Transparent)

Adhesive inhibited :

Use the attached flexible hose and hose band for

connecting the drain hose to the clear drain socket.

If applying the adhesive, socket will be damaged and

cause water leakage.

Align the attached hose band to

the end of hose, set the

tightening position upward, and

then tighten it.

Flexible hose

(Accessory)

Socket for VP25 vinyl chloride pipe

(To be local procure)

Drain pipe

connecting port

(Hard socket)

VP25 vinyl chloride pipe

(To be local procure)

Attached hose

band

Attached flexible hose

Soft socket

Hard socket

Socket for VP25

(To be local procure)

VP25 vinyl chloride

pipe (To be local

procure)

Indoor

unit

Indoor

unit

13-EN