1 8

Figure PD-2 – Model CVGF Cooling Only Without Unit
Mounted Starter (for Remote Mounted Starter)

Figure PD-1 – Model CVGF Cooling Only
With Unit Mounted Starter

Physical
Dimensions

50 and 60 Hz SI
(English Units)

Dimensions – SI Units (English Units)

Clearance

Unit Dimensions

Unit Dimensions

Tube Pull

With Unit Mounted Starters

Without Unit Mounted Starters

Comp.

Shell Size

CL1

CL2

Length

Height

Width

Width

400-500

500

4235 mm

1118 mm

4083 mm

2094 mm

1984 mm

1929 mm

(13’ 10

3

/

4

”)

(3’ 8”)

(13’ 4

3

/

4

”)

(6’ 10

1

/

2

”)

(6’ 6

1

/

8

”)

(6’ 3

15

/

16

”)

500

700

4235 mm

1850 mm

4083 mm

2200 mm

2038 mm

1988 mm

(13’ 10

3

/

4

”)

(3’ 11”)

(13’ 4

3

/

4

”)

(7’ 2

5

/

8

”)

(6’ 8

1

/

4

”)

(6’ 6

1

/

4

”)

650

700

4235 mm

1850 mm

4083 mm

2270 mm

2083 mm

2076 mm

(13’ 10

3

/

4

”)

(3’ 11”)

(13’ 4

3

/

4

”)

(7’ 5

3

/

8

”)

(6’ 10”)

(6’ 9

3

/

4

”)

800-1000

1000

4235 mm

1219 mm

4083 mm

2521 mm

2305 mm

2257 mm

(13’ 10

3

/

4

”)

(4’)

(13’ 4

3

/

4

”)

(8’3

1

/

4

”)

(7’6

3

/

4

”)

(7’ 4

7

/

8

”)

CL1 at either end of machine and is required for tube pull clearance.
CL2 is always at the opposite end of machine from CL1 and is for water box plus clearance.
– Recommended clearance (D1) for machine with unit mounted starter is 914 mm (36”)
– Recommended clearance (D2) for machine without unit mounted starter is 1219 mm (38”)
Unit length is not included for the waterbox.
See page 19 for waterbox dimension

HEIGHT

WIDTH

914 mm (36

)

RECOMMENDED

CLEARANCE

457 mm (18')

RECOMMENDED

CLEARANCE

LENGTH

914 mm (36

)

RECOMMENDED

CLEARANCE

HEIGHT

WIDTH