3 communication parameters – Toshiba Tosvert Inverter E6580772 User Manual
Page 13
E6580772
12
3.1.3 Communication parameters
F10M communication parameters
Parameter name
Title
Setting value
Details
Inverter number
f802
0
to 255
Sets inverter station address. (Note 1)
When using a message transmission, set the address of the
master station to 0 and address of the inverter station to 1 or
over.
Data type
selection
f830
0
, 1
Selects type of transmitting and receiving data.
0: VFA7 mode
1
:μs 250 mode
Input reference
setting 1
f831
Input reference
setting 2
f832
Input reference
setting 3
f833
Input reference
setting 4
f834
Input reference
setting 5
f835
Input reference
setting 6
f836
0
to 16
Sets scan transmission data to be received.
0
: Without setting
1
: Command
2
: Speed reference value
3
: Auxiliary speed reference value
4
: Torque limit value
5
: Positive torque limit value
6
: Negative torque limit value
7
: Torque command value
8
: Synchronized torque bias
9
: Tension torque bias
10
: Load sharing gain
11
: Drooping gain
12
: Speed loop proportional gain
13
: Speed loop accumulative gain
14
: Terminal output data
15
: Inertia moment ratio
16
: Expansion command
Monitor output
setting 1
f841
Monitor output
setting 2
f842
Monitor output
setting 3
f843
Monitor output
setting 4
f844
Monitor output
setting 5
f845
Monitor output
setting 6
f846
0
to 16
Sets scan transmission data to be sent.
0
: Without setting
1
: Status
2
: Operation frequency
3
: Speed feedback value (real time)
4
: Speed feedback value (1-second filter)
5
: Internal torque reference value
6
: Output amperage
7
: Exciting amperage
8
: Torque amperage
9
: Overload accumulative value
10
: Deleted torque of acceleration/deceleration torque
11
: Motor counter data
12
: Error code
13
: Input terminal data
14
: VI input
15
: RR input
16
: RX input